| Date |
Text |
| 2005-03-17 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | FBC-2001 BUILDING |
| | |
| | 1) SUBMIT A DETAIL FOR ACCESSIBLE BATH- |
| | ROOMS PER SECTIONS 11-4.16, 11-4.19, 11- |
| | 4.21, 11-4.22 AND ALL SUBSECTIONS. |
| | 2) SHT A3.2 THE SANITARY RISER DIAGRAM |
| | DOES NOTMEET CODE REQUIREMENTS. THE |
| | SERVICE SINK SHALL DISCHARGE DOWNSTREAM |
| | OF THE BATHROOM FIXTRUES. SECTION 909.1 |
| | 3) AN RPZ BACKFLOW IS REQUIRED ON THE |
| | WATER SERVICE. SECTION 608.13.2. |
| | 4) A DRINKING FOUNTAIN IS REQUIRED PER |
| | TABLE 403.1. SUBMIT DETAIL SHOWING |
| | COMPLIANCE WITH 11-4.15 AND ALL |
| | SUBSECTIONS. |
| | 5) SUBMIT DETAIL FOR CONDENSATE PIPING. |
| | SHOW PIPE SIZE, MATERIAL, SUPPORT DETAIL |
| | & TERMINATION POINT. SECTION 104.3.1.1. |
| | 6) PLANS NOT HAVE A NEW ARCHITECT OF |
| | RECORD, AND PLANS PREVIOUSLY SUBMITTED |
| | FOR PLUMBING WERE SIGNED/SEALED/DATED BY |
| | AN ENGINEER. PLEASE SUBMIT A |
| | SIGNED/SEALED/DATED NOTORIZED LETTER FOR |
| | CHANGING ARCHITECTS AND REMOVING THE |
| | ENGINEER OF RECORD FROM THIS JOB. PLEASE |
| | SUBMIT TWO COMPLETE SETS OF PLANS FOR |
| | REVIEW AND FOR PUBLIC RECORD. |
| | |