| 2005-03-24 00:00:00 | PERMIT #04061232 |
| | |
| | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | 1.)TYPE IV IS DECLARED ON THE COVER |
| | SHEET.WOOD COLUMNS ARE SHOWN ON A1.0. |
| | ALSO A1.0 STATES THAT THE FLOOR FINISH |
| | IS WOOD, BUT A1.1 NOTES AN EXISTING WOOD |
| | DECK.IS THE WOOD FLOOR NOTED A FLOOR |
| | FINISH OR THE FLOOR FRAMING?OUR PLANS |
| | CURRENTLY ON FILE SHOW WOOD JOISTS FOR |
| | THE FLOOR FRAMING.SEE FBC606 REGARDING |
| | DEFINITION OF TYPE IV BUILDING. |
| | |
| | 2.)THE COVER SHEET SHOWS 5739 SF FOR |
| | FIRST FLOOR TWICE.PLEASE NOTE SECOND |
| | FLOOR SQUARE FOOTAGE. |
| | |
| | 3.)SHEET A1.0 HAS A NOTE REGARDING A 1 |
| | HOUR SEPARATION.WHAT IS THE PURPOSE OF |
| | THIS SEPARATION?HOW WILL THE 1 HOUR |
| | SEPARATION BE MAINTAINED WHERE THE WOOD |
| | COLUMNS MEET THE BOTTOM OF THE FLOOR |
| | CEILING ASSEMBLY?A FREIGHT LIFT IS |
| | SHOWN ON A1.0; PROVIDE 1 HR FIRE RATING |
| | INFORMATION. |
| | |
| | 4.)SHEET A1.0 BOTTOM RIGHT CORNER OF |
| | PLAN SHOWS 1HR ENCLOSURE (SEE DETAIL). |
| | NO DETAIL PROVIDED AND IT IS UNCLEAR HOW |
| | THE 1 HR SEPARATION IS MAINTAINED |
| | BETWEEN THE FIRST AND SECOND FLOORS AS |
| | THE FLOOR PLAN SHOWS A WALL WHICH DOES |
| | NOT ENCLOSE THE STAIRS. |
| | |
| | 5.)THERE IS A NOTE ON SHEET A1.3 THAT |
| | ALL EXTERIOR OPENINGS ARE EXISTING. |
| | OPENINGS AFFECTED BY THE SCOPE OF WORK |
| | ON THIS PERMIT ARE TO BE CODE COMPLIANT |
| | AND SHOW COMPLIANCE ON THE PLAN.ALSO |
| | THERE IS A NEW DOOR SHOWN. |
| | |
| | 6.)PLEASE SEE FBC1006.1.3.2.IF THIS |
| | BUILDING IS A TYPE V, THE STAIRWAY AT |
| | THE TOP LEFT IS TO HAVE 3 HR PROTECTION. |
| | |
| | 7.)BASED ON PROPERTY APPRAISER?S |
| | VALUATION, THIS IS AN OVER 50% |
| | IMPROVEMENT, FBC3401.7.2.6. |
| | |
| | 8.)OPENINGS IN THE EXIT STAIR ARE |
| | PROHIBITED EXCEPT AS NOTED IN |
| | FBC1006.1.3.1 (WINDOW SHOWN IN |
| | STAIRWAY). |
| | |
| | 9.)SHOW OPENING PROTECTIVES FOR THE |
| | STAIRS AS REQUIRED BY FBC TABLE 705.1.2. |
| | |
| | 10.)DOOR 2, 1ST FLOOR, DOES NOT APPEAR |
| | TO LEAD ANYWHERE.IF IT IS AN OPENING |
| | INTO THE STAIR, INDICATE OPENING |
| | PROTECTIVE REQUIREMENT. |
| | |
| | 11.) PROVIDE TEST REPORTS AND FLORIDA |
| | STATE OR LOCAL PRODUCT APPROVAL FOR THE |
| | NEW EXTERIOR DOOR. |
| | |
| | 12.) PROVIDE GUARDRAIL AND HANDRAIL |
| | DETAILS.NOTE DESIGN CRITERIA IN |
| | COMPLIANCE WITH FBC1608.1.1 (HANDRAIL) |
| | AND FBC 1608.2.2 (GUARDRAIL).COMPLY |
| | WITH ALL REQUIREMENTS OF FBC CHAPTERS 10 |
| | AND 11. |
| | |
| | 13.) PROVIDE ACCESSIBILITY DETAILS; |
| | ACCESSIBLE ENTRY, BATHROOM DETAILS |
| | INCLUDING DIMENSIONS FOR GRAB BARS, LAV, |
| | WC FBC CHAPTER 11. |
| | |
| | 14.) PROVIDE LOADING INFORMATION FOR |
| | ROOFTOP MECHANICAL EQUIPMENT, DESIGN |
| | LOAD LIMITATIONS OF EXISTING ROOF. |
| | |
| | 15.) ENERGY CALCS REQUIRED, FBC13. |
| | |
| | 16.) VERTICAL ACCESSIBILITY REQUIRED, |
| | FBC11-4.1.3. |
| | |
| | 17.) PROVIDE DESIGN PRESSURES FOR THE |
| | EXTERIOR DOOR AND DESIGN CRITERIA |
| | FBC1606.1.7. |
| | |
| | 18.) DMP REVIEW REQUIRED.WHEN |
| | RESUBMITTING, PLEASE INDICATE THAT A |
| | ZONING REVIEW IS REQUIRED ON THE |
| | RESUBMITTAL SHEET TO HELP EXPEDITE PLAN |
| | REVIEW. |