| 2004-10-25 00:00:00 | ********* UNSAT *********** |
| | |
| | 1)NOTE: PLEASE SEE NOTE#4 FROM PREVIOUS |
| | REVIEW. A GROUNDING ELECTRODE SYSTEM |
| | IS NOW SHOWN, HOWEVER SIZING OF GEC IS |
| | TO BE SIZED FOR THE PARALLEL 4/0'S |
| | PER 250.66. SHOWS A #3, WHICH IS NOT |
| | LARGE ENOUGH. |
| | |
| | 2)NOTE : PLEASE SEE NOTE # 5FROM |
| | PREVIOUS REVIEW. PLEASE SEE MISSING |
| | LICENSE # FOR FIRM ONA-SHEETS. |
| | PLEASE SEE FAC 61G1-16.004 AND FS 481.- |
| | .219. |
| | THIS IS REQUIRED, WHEATHER OR NOT |
| | COMMENT IS MADE BY OTHER REVIEWER(S). |
| | |
| | 3)NOTE: PLEASE SEE LOAD FOR WASHER/DRYER |
| | IS SHOWN AS 7KW ON A 2P-30A BRKR FOR |
| | OCP. |
| | PLEASE ALSO SEE 11KW LOAD SHOWN ON A |
| | 2P-30A BRKR FOR ELEVATOR. |
| | |
| | 4)NOTE: PLEASE CLARIFY MISSING EQUIPMENT |
| | GROUNDING CONDUCTORS FROM MAIN TO PANEL |
| | AND FROM PANEL A TO B. |
| | 250.110,250.122 |
| | |
| | 5)NOTE: PLEASE SEE MAIN DISCONNECT IS |
| | SHOWN AS MLO. APPEARS TO BE A MISPRINT?? |
| | |
| | |
| | PLEASE SEE POSSIBLE COMMENTS FROM OTHER |
| | REVIEWERS WHICH MAY HAVE AN AFFECT ON |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | AND INSERT NEW SHEETS INTO COMPLETED |
| | SETS FOR REVIEW AND STAMPING. |
| | ONE COPY OF OLD SHEETS SHOULD BE SUBMITT |
| | -ED FOR REFERENCE ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |