| Plan Review Notes For Permit 04061232 |
| Permit Number |
04061232 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-09-15 00:00:00 | 1) DOOR # 31 IS NOT LABELED PER THE | | | DOOR SCHEDULE. THIS DOOR IS LOCATED | | | IN A RATED ENCLOSURE. PLEASE REVISE | | | DOOR SCHEDULE AS NECESSARY. | | | | | | 2) NEW FIRE ALARM SYSTEM SHALL BE | | | UL LISTED FOR "CENTRAL STATION | | | SERVICE" AND BE THIRD PARTY | | | CERTIFICATED. | | | | | | 3) DUCT SMOKE DETECTORS SHALL CAUSE | | | AN ALARM NOT A SUPERVISORY SIGNAL | | | AS NOTED IN 2 C) ON PAGE FA3-3. | | | SEPARATE PLANS AND PERMITS REQUIRED | | | FOR THE NEW FIRE ALARM SYSTEM. | | | | | | 4) SEPARATE PLANS AND PERMITS | | | REQUIRED FOR FIRE SPRINKLER REMODEL. | | | THE NEW FDC IS TO BE LOCATED WITHIN | | | 150 FEET OF A FIRE HYDRANT. | | | | | | 5) COULD NOT LOCATE ANY FIRE | | | EXTINGUISHER LOCATIONS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|