| Date |
Text |
| 2004-07-14 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | FBC-2001 BUILDING |
| | |
| | 1) SUBMIT CALCULATIONS FOR MINIMUM FAC- |
| | ILITIES FOR FIXTURES PER TABLES 1103.1 |
| | (BLDG.) AND 403.1 (PLUMB.) SHOW SQUARE |
| | FOOTAGE FOR EACH OCCUPANCY, BUSINESS, |
| | INDUSTRIAL, & STORAGE. |
| | 2) INDICATE TYPE AND AMOUNT OF MATERIALS |
| | TO BE STORED. RESPONSE MAY CREATE NEW |
| | COMMENTS. SECTION 104.2.1 |
| | 3) WHAT TYPE OF BUSINESS/WORK WILL BE |
| | DONE IN THIS SPACE? |
| | 4) PRIVATE BATHROOM SHALL BE ADAPTABLE. |
| | SUBMIT A DETAIL SHOWING BACKING FOR W/C |
| | GRAB BARS, SIZE OF OPENING FOR W/C, THE |
| | BACKING FOR GRAB BARS FOR THE SHOWER, |
| | CONTROL AREA FOR SHOWER, HEIGHT OF SEAT |
| | AND BACKING FOR SEAT, & CURB HEIGHT. |
| | SECTION 11-4.1.3(11).- ALSO INDICATE |
| | TURNING AREA IN ADAPTABLE BATHROOM. |
| | 5) SUBMIT A DETAIL FOR ACCESSIBLE BATH- |
| | ROOMS PER SECTIONS 11-4.16, 11-4.19, 11- |
| | 4.21 AND ALL SUBSECTIONS. |
| | 6) DOORS REQUIRED TO BE ACCESSIBLE SHALL |
| | COMPLY WITH THE REQUIREMENTS OF 11-4.13. |
| | AND 11-4.13.5. THE CLEAR WIDTH OF 32" |
| | CAN NOT BE ACHIEVED WITH A 2'8" DOOR. |
| | 7) LUNCH ROOM SINK SHALL BE ACCESSIBLE |
| | PER SECTION 11-4.24. SUBMIT A DETAIL |
| | SHOWING COMPLIANCE WITH THIS SECTION AND |
| | ALL SUBSECTIONS. |
| | 8) SHT PO-01 WATER RISER DIAGRAM & NOTES |
| | AIR CHAMBERS ARE NOT APPROVED. DELETE |
| | FROM RISER AND NOTES. WATER HAMMER ARR- |
| | ESTORS REQUIRED BY SECTION 604.9, (AT |
| | ICE MAKERS, WASH MACHINES, & DISHWASHERS |
| | SHALL BE LOCATED NEAR THE FIXTURES IN AN |
| | "EFFECTIVE RANGE PER PDI-WH 201 AND |
| | MANUF. - RISER DIAGRAM DOES NOT REFLECT |
| | THE FLOOR PLAN. THERE ARE FIXTURES NOT |
| | SHOWN ON FLOOR PLAN, (TUB & LAV). |
| | 9) SHT P0-01 THE SANITARY RISER DIAGRAM |
| | DOES NOT REFLECT THE FLOOR PLAN, NOT |
| | DOES IT MEET CODE REQUIREMENTS. W/C'S |
| | (A) W/C'S SHALL NOT BE DOUBLE TRAPPED. |
| | SECTION 1002.1. W/C'S HAVE AN INTEGRAL |
| | TRAP. SEE EXCEPTION (1). |
| | (B) SANITARY CROSS FITTINGS ARE NOT |
| | APPROVED FOR UNDERGROUND USE. SECTION |
| | 706.3. |
| | (C) HORIZONTAL DRY VENTS ARE NOT APPRO- |
| | VED PER SECTION 905.3 |
| | (D) TEE FITTINGS ARE NOT APPROVED FOR |
| | USE AS SHOWN AT THE TOP OF RISER WITH |
| | DRAINAGE FROM BOTH DIRECTIONS. TABLE |
| | 706.3. |
| | (E) NO BATH TUB IN ROOM 206 SHOWN ON |
| | THE FLOOR PLAN. SECTION 104.2.1 |
| | (F) 2 LAVS SHOWN ON RISER, BUT ONLY ONE |
| | SHOWN ON FLOOR PLAN. SECTION 104.2.1. |
| | (G) WASH MACHINE REQUIRES A TRAP AND A |
| | STANDPIPE. SECTIONS 1002.1, & 802.4. |
| | (H) DISHWASHERS REQUIRE AN AIR GAP FIT- |
| | TING ABOVE THE FLOOR RIM LEVEL OF THE |
| | SINK. |
| | (I) WHAT IS THE FIXTURE BETWEEN THE |
| | DISHWASHER AND THE SINK IN THE LUNCHROOM |
| | WHAT IS THE USAGE OF THIS FIXTURE. SECT- |
| | ION 104.2.1. |
| | (J) THE RISER DIAGRAM SHALL REFLECT THE |
| | LAYOUT OF THE FIXTURES ON THE FLOOR PLAN |
| | AND THE ACTUAL INSTALLATION OF THE PIP- |
| | ING. SEE RED LINE CORRECTIONS AND EXAMP- |
| | LE. |
| | 10) AN RPZ BACKFLOW IS REQUIRED ON THE |
| | WATER SERVICE. SECTION 608.13.2 |
| | 11) THERMAL EXPANSION CONTROL IS REQUIR- |
| | ED PER SECTION 607.3.2 |
| | 12) A PROFESSIONAL ENGINEER SHALL SIGN |
| | HIS NAME AND AFFIX HIS SEAL TO ALL PLANS |
| | SPECIFICATIONS, REPORTS AND FINAL BID |
| | DOCUMENTS PROVIDED TO THE OWNER OR THE |
| | OWNER'S REPRESENTATIVE, OR OTHER DOCU- |
| | MENTS PREPARED OR ISSUED BY SAID REGIS- |
| | TRANT AND BEING FILED FOR PUBLIC RECORD. |
| | THE DATE THAT THE SIGNATURE AND SEAL IS |
| | AFFIXED AS PROVIDED HEREIN SHALL BE EN- |
| | TERED ON SAID PLANS, SPECIFICATIONS, RE- |
| | PORTS, OR OTHER DOCUMENTS IMMEDIATELY |
| | UNDER THE SIGNATURE OF THE PROFESSIONAL |
| | ENGINEER, FAC 61G15-23.002(1) |
| | FS 471.025 |
| | EACH SHEET OF PLANS AND PRINTS WHICH |
| | MUST BE SEALED UNDER THE PROVISIONS OF |
| | CHAPTER 471 SHALL BE SEALED, SIGNED AND |
| | DATED BY THE PROFESSIONAL ENGINEER IN |
| | RESPONSIBLE CHARGE. FAC 61G15-23.002(2) |
| | FS 471.025 |
| | ENGINEERS SHALL LEGIBLY INDICATE THEIR |
| | NAME, ADDRESS AND LICENSE NUMBER ON EACH |
| | SHEET. IF PRACTICING THROUGH A DULY |
| | AUTHORIZED ENGINEERING BUSINESS, ENGIN- |
| | EERS, ENGINEERS SHALL LEGIBLY INDICATE |
| | THEIR NAME AND LICENSE NUMBER, AS WELL |
| | AS, THE NAME, ADDRESS AND CERTIFICATE OF |
| | AUTHORIZATION NUMBER OF THE ENGINEERING |
| | BUSINESS ON EACH SHEET. A TITLE BLOCK |
| | WILL SATISFY THIS REQUIREMENT. FAC |
| | 61G15-23.002(2) - FS 471.025 |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |