| Date |
Text |
| 2004-06-25 00:00:00 | ************* UNSAT ************* |
| | |
| | 1)NOTE: PLEASE SEE ELECTRICAL PLANS |
| | APPEAR TO BE SHOWN ON A-SHEETS LABELED |
| | AS REFLECTED CEILING PLANS?? |
| | |
| | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 3 )NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| | PLEASE SHOW PER |
| | 220.3,220.10,220.11,220.13 ETC. |
| | PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| | AT 125% PER 215.3,230.42 |
| | |
| | 4)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED |
| | PANEL SCHEDULE. 215.5 |
| | PLEASE ALSO SEE 700.12E |
| | |
| | 5)NOTE: PLEASE SEE PLANS MUST CONTAIN |
| | LEGAL SIGNATURE AS SHOWN ON SEAL. |
| | PLANS APPEAR TO CONTAIN INITIALS. |
| | IF THIS IS INDEED "LEGAL" SIGNATURE, |
| | PLEASE PROVIDE A COMPLETED SIGNED, DATED |
| | AND SEALED NOTORIZED LETTER. PLEASE BE |
| | SURE NOTORY INCLUDES ALL INFORMATION AS |
| | REQUIRED. |
| | PLEASE SEE FS 481.221, WHICH REQUIRES |
| | SIAGNTURE. |
| | |
| | 6)NOTE: PLEASE SEE FAC 61G1-16.004, |
| | AND FS 481.219. |
| | PLEASE INCLUDE ALL LICENSE #'S ON TITLE |
| | BLOCK AS REQUIRED PER ABOVE. |
| | |
| | 7)NOTE: PLEASE INCLUDE GROUNDING ELEC- |
| | -TRODE SYSTEM. 250.50. NO DETAIL GIVEN. |
| | |
| | 8)NOTE: PLEASE SHOW A/C EQUIPMENT ON |
| | PLANS AND DISC'S PER 440.11 |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SEE COMMENTS FROM OTHER REVIEWERS |
| | AS THEY MAY AFFECT ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |