| Date |
Text |
| 2006-05-02 00:00:00 | ********* UNSAT *********** |
| | |
| | 1) NOTE: PLEASE SEE TWO SEPARATE |
| | ELECTRICAL RISERS ARE NOW BEING |
| | SUBMITTED. |
| | ONE INDICATES BEING FOR 626 FRANKLIN AND |
| | THE OTHER FOR 826 FRANKLIN. |
| | PLEASE ONLY SUBMIT ONE FOR REVIEW. |
| | PLEASE SEE ONE RISER SHOWS #6 FOR GEC |
| | AND #4, PLEASE SEE 250.66, AS THE #4 IS |
| | REQUIRED AT A MIN. |
| | |
| | 2) NOTE: PLEASE ALSO EACH RISER CONTAINS |
| | DIFFERENT PERSONS RESPONSIBLE FOR DESIGN |
| | PLEASE SEE THE ORIGINAL PERSON |
| | RESPONSIBLE FOR DESIGN SHOULD BE THE |
| | PERSON OF RECORD , UNLESS ALL PLANS ARE |
| | BEING CHANGED TO THE NEW DESIGN |
| | PROFESSIONAL OF RECORD. |
| | FBC104.2.1 |
| | PLEASE SEE IN ANY CASE ALL PLANS, WHEN |
| | NOT ORIGINALLY DONE BY AN ARCHITECT OR |
| | ENGINEER, SHALL CONTAIN THE PRINTED NAME |
| | AND SIGNATURE. |
| | |
| | 3) NOTE: PELASE SEE PREVIOUS NOTE |
| | MENTIONED THE DEDICATE BATH CIRCUIT |
| | SHALL BE 20A AND #12, THIS WAS CORRECTED |
| | TO #12, HOWEVER IS NOW ALSO PENCILED AS |
| | #14? |
| | PLEASE KNOW, ONLY 20A AND #12 IS |
| | PERMITTED. |
| | |
| | 4) NOTE: PLEASE SEE ONE PLANS INDICATES |
| | ELECTRICAL FOR ALL APPLIANCES, WHERE THE |
| | OTHER SHOWS GAS FOR SOME. |
| | PLEASE CORRELATE AND SUBMIT ONLY ONE. |
| | 215.5 |
| | |
| | 5) NOTE; PLEASE SEE THE PLANS CAME IN AS |
| | A SUBMITTIAL WHEN INDEED IT WAS A |
| | REVISION. PLEASE SEE A FEE IS OWED FOR |
| | THIS REVIEW AND ALSO FOR REVISION WHEN |
| | PLANS ARE BROUGHT BACK. |
| | PLEASE BE SURE TO ADDRESS ALL COMMENTS |
| | AND IF THERE ARE ANY QUESTIONS, PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS |
| | OFFICE TO HELP ALLEAVIATE ANY FURTHER |
| | DELAYS/REVIEWSOR FEES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |