2006-01-17 00:00:00*********UNSAT **********
  
  
 1)NOTE: PLEASE SEE PLANS HAVE HAD ALL
 REQUIRED SMOKE DETECTORS AND GFI'S FOR
 EXISTING DWELLING REMOVED.????
 PLEASE SEE ORIGINAL PLANS WHICH
 INDICATED THIS.
 FBC CHAPTER 34 FOR ADDTIONS TO EXISTING
 DWELLINGS.
 PLEASE CORRECT PLANS.
  
 2)NOTE: PLEASE CORRELATE PANEL SCHEDULE
 ALONG WITH LOAD CALCUALTIONS SUBMITTED.
 PLEASE SEE DRYER SHOWN AS 5KW ON A
 1-POLE 20 ETC.
 PLEASE SEE AHU #2 AS 30A OCP #10 AWG
 WITH 10 KW RATING ON CALCS.(424.3).
 PLEASE SEE MISSING MICROWAVE.
 ETC.
 215.5
  
 3)NOTE: PLEASE SEE MIN OCP FOR DOUBLE
 OVEN AND COOKTOP SHALL BE BASED ON MIN
 OCP FOR KW RATINGS. PLEASE SEE A 10KW
 LOAD IS BEING SHOWN ON 40A OCP WHICH
 EXCEEDS MIN RATINGS OF DEVICE AND BRKR.
 240.4, 215.5
  
 4)NOTE: PLEASE SEE 210.52D,210.11C3
 WHICH REQUIRES BATH RECEPT(S) TO BE ON A
 MIN 20A, #12 AWG CIRCUIT.
  
 5)NOTE: PLEASE INDICATE THE REQUIRED GFI
 PROTECTION FOR THE JACUZZI TUB,680.71
  
 6)NOTE: PLEASE SEE 210.52C1 FOR WHAT
 APPEARS TO BE A MISSING KITCHEN
 COUNTERSPACE RECEPT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  