| 2006-01-17 00:00:00 | *********UNSAT ********** |
| | |
| | |
| | 1)NOTE: PLEASE SEE PLANS HAVE HAD ALL |
| | REQUIRED SMOKE DETECTORS AND GFI'S FOR |
| | EXISTING DWELLING REMOVED.???? |
| | PLEASE SEE ORIGINAL PLANS WHICH |
| | INDICATED THIS. |
| | FBC CHAPTER 34 FOR ADDTIONS TO EXISTING |
| | DWELLINGS. |
| | PLEASE CORRECT PLANS. |
| | |
| | 2)NOTE: PLEASE CORRELATE PANEL SCHEDULE |
| | ALONG WITH LOAD CALCUALTIONS SUBMITTED. |
| | PLEASE SEE DRYER SHOWN AS 5KW ON A |
| | 1-POLE 20 ETC. |
| | PLEASE SEE AHU #2 AS 30A OCP #10 AWG |
| | WITH 10 KW RATING ON CALCS.(424.3). |
| | PLEASE SEE MISSING MICROWAVE. |
| | ETC. |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE SEE MIN OCP FOR DOUBLE |
| | OVEN AND COOKTOP SHALL BE BASED ON MIN |
| | OCP FOR KW RATINGS. PLEASE SEE A 10KW |
| | LOAD IS BEING SHOWN ON 40A OCP WHICH |
| | EXCEEDS MIN RATINGS OF DEVICE AND BRKR. |
| | 240.4, 215.5 |
| | |
| | 4)NOTE: PLEASE SEE 210.52D,210.11C3 |
| | WHICH REQUIRES BATH RECEPT(S) TO BE ON A |
| | MIN 20A, #12 AWG CIRCUIT. |
| | |
| | 5)NOTE: PLEASE INDICATE THE REQUIRED GFI |
| | PROTECTION FOR THE JACUZZI TUB,680.71 |
| | |
| | 6)NOTE: PLEASE SEE 210.52C1 FOR WHAT |
| | APPEARS TO BE A MISSING KITCHEN |
| | COUNTERSPACE RECEPT. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |