Plan Review Notes
Plan Review Notes For Permit 04061202
Permit Number 04061202
Review Stop E
Sequence Number 3
Notes
Date Text
2004-08-10 00:00:00************* UNSAT *****************
  
 1)NOTE: PLEASE SEE PLANS ARE NOW BEING
 SUBMITTED WITH REFERENCE TO SERVICE AS
 BEING A NEW 200A SERVICE. PLEASE SEE
 NOTE #4 FROM PREVIOUS REVIEW WHICH
 REQUESTED AIC RATING FOR NEW SERVICE
 MAIN/EQIPMENT. PER 110.9/215.5
 PLEASE SHOW LOCATION OF NEW PANEL.
  
 2)NOTE: PLEASE SEE PLANS ARE ALSO NOW
 BEING SUBMITTED SHOWING ALL NEW ELECTR-
 -ICAL IN REMAINDER OF HOUSE?
 IF ELECTRICAL NOW SHOWN FOR EXISTING
 DWELLINGIS EXISTING, PLEASE LABEL W/
 AN "E" OR NOTE. AS SHOWN, EXISTING
 DWELLING IS BEING REWIRED?
  
 3) NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 4)NOTE: PLEASE SEE PANEL/LOAD CALCS
 INDICATE TWO A/C SYSTEMS YET PLANS ONLY
 SHOW ONE COND UNIT AND AHU?
  
 PLEASE SEE SOME NOTES ARE NEW DUE TO
 PLANS BEING CHANGED TO SHOW NEW ITEMS.
 AIC RATING WAS REQUESTED ON PREVIOUS
 REVIEW FOR SERVICE (IF NEW).
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  