| 2004-08-10 00:00:00 | ************* UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE SEE PLANS ARE NOW BEING |
| | SUBMITTED WITH REFERENCE TO SERVICE AS |
| | BEING A NEW 200A SERVICE. PLEASE SEE |
| | NOTE #4 FROM PREVIOUS REVIEW WHICH |
| | REQUESTED AIC RATING FOR NEW SERVICE |
| | MAIN/EQIPMENT. PER 110.9/215.5 |
| | PLEASE SHOW LOCATION OF NEW PANEL. |
| | |
| | 2)NOTE: PLEASE SEE PLANS ARE ALSO NOW |
| | BEING SUBMITTED SHOWING ALL NEW ELECTR- |
| | -ICAL IN REMAINDER OF HOUSE? |
| | IF ELECTRICAL NOW SHOWN FOR EXISTING |
| | DWELLINGIS EXISTING, PLEASE LABEL W/ |
| | AN "E" OR NOTE. AS SHOWN, EXISTING |
| | DWELLING IS BEING REWIRED? |
| | |
| | 3) NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210.8A-6 |
| | |
| | 4)NOTE: PLEASE SEE PANEL/LOAD CALCS |
| | INDICATE TWO A/C SYSTEMS YET PLANS ONLY |
| | SHOW ONE COND UNIT AND AHU? |
| | |
| | PLEASE SEE SOME NOTES ARE NEW DUE TO |
| | PLANS BEING CHANGED TO SHOW NEW ITEMS. |
| | AIC RATING WAS REQUESTED ON PREVIOUS |
| | REVIEW FOR SERVICE (IF NEW). |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |