2004-07-19 00:00:00************* UNSAT ***************
  
 1)NOTE: PLEASE CORRELATE PANEL SCHEDULE
 AND LOAD CALCULATIONS. THERE ARE MANY
 ITEMS THAT DO NOT MATCH.
 PLEASE SEE AHU KW RATING SHOWN AS 10KW
 W/60OCP AND 30A OCP? 424.3B
 PLEASE SEE WATER HEATER, DISP,DISHW ETC.
  
 2)NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
 MUST BE 20A #12.
  
 NOTE: OK
  
  
  
 4)NOTE: PLEASE CLARIFY IF SERVICE IS
 NEW OR EXSITING? METER IS SHOWN AS EXIST
 -ING BUT PANEL DO NOT INDICATE. IF NEW
 SUBMIT AIC RATING FOR EQUIPMENT PER
 110.9.
 PLEASE ALSO SEE MISSING EQUIPMENT GROUND
 -ING CONDUCTOR PER 250.110,250.24,
 250.122
  
 5)NOTE: PLEASE SEE FBC CHAPTER 34 FOR
 ADDITIONS TO EXISTING DWELLINGS.
 PLEASE PROVIDE LAYOUT FOR NEW OR EXIST-
 -ING SD'S , GFI'S ETC.
 3401.7.1.2.1
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]