| Plan Review Notes For Permit 04061202 |
| Permit Number |
04061202 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-07-19 00:00:00 | ************* UNSAT *************** | | | | | | 1)NOTE: PLEASE CORRELATE PANEL SCHEDULE | | | AND LOAD CALCULATIONS. THERE ARE MANY | | | ITEMS THAT DO NOT MATCH. | | | PLEASE SEE AHU KW RATING SHOWN AS 10KW | | | W/60OCP AND 30A OCP? 424.3B | | | PLEASE SEE WATER HEATER, DISP,DISHW ETC. | | | | | | 2)NOTE: PLEASE LIST ALL THE REQ'D | | | DEDICATED BATH(S) CIRCUIT(S) ON PANEL | | | SCHEDULE. PER 210.52D, 210.11C3 | | | MUST BE 20A #12. | | | | | | NOTE: OK | | | | | | | | | | | | 4)NOTE: PLEASE CLARIFY IF SERVICE IS | | | NEW OR EXSITING? METER IS SHOWN AS EXIST | | | -ING BUT PANEL DO NOT INDICATE. IF NEW | | | SUBMIT AIC RATING FOR EQUIPMENT PER | | | 110.9. | | | PLEASE ALSO SEE MISSING EQUIPMENT GROUND | | | -ING CONDUCTOR PER 250.110,250.24, | | | 250.122 | | | | | | 5)NOTE: PLEASE SEE FBC CHAPTER 34 FOR | | | ADDITIONS TO EXISTING DWELLINGS. | | | PLEASE PROVIDE LAYOUT FOR NEW OR EXIST- | | | -ING SD'S , GFI'S ETC. | | | 3401.7.1.2.1 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|