| Plan Review Notes For Permit 04061180 |
| Permit Number |
04061180 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-08-02 00:00:00 | DENIED | | | SAME COMMENTS FROM PREVIOUS REVIEW. | | | | | | 2.PLEASE SIGN OWNER/AGENT ON BOTH | | | COPIES OF ENERGY CALCS. | | | | | | 5.FBC1015.2 HEIGHT. GUARDRAILS SHALL | | | FORM A VERTICAL PROTECTIVE BARRIER NOT | | | LESS THAN 42" HIGH. | | | FBC 1015.3 OPENINGS.OPEN | | | GUARDRAILS SHALL HAVE INTERMEDIATE | | | RAILS OR ORNIMENTAL PATTERNS SUCH AS A | | | 4" DIAMETER SPHERE CAN NOT PASS THROUGH. | | | A BOTTOM RAIL OR CURB SHALL BE PROVIDED | | | THAT WILL REJECT THE PASSAGE OF A 2" | | | DIAMETER SPHERE.SHOW DETAIL ON PLANS. | | | | | | LOOK FOR COMMENTS BY THE OTHER PLAN | | | REVIEW DISCIPLINES THAT MAY BE WRITTEN | | | ON THE APPLICATION, PLANS, OR ATTACHED | | | SEPARATELY. WHEN RESUBMITTING PLANS | | | PLEASE CLEARLY INDICATE THE REVISION AND | | | REMOVE AND REPLACE ANY PAGES AS NECESS- | | | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH | | | THE PLANS WHEN RESUBMITTING PLANS. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW NUMBER, WITH A DESCRIPTION OF THE | | | REVISION MADE, IDENTIFYING THE SHEET OR | | | SPECIFICATION PAGE WHERE THE CHANGES CAN | | | BE FOUND, WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | ART LANGE | | | BUILDING PLAN REVIEW | | | TEL: (561)805-6672 | | | FAX: (561)659-8026 |
|