| Plan Review Notes For Permit 04061180 |
| Permit Number |
04061180 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-07-13 00:00:00 | NO MECHANICAL PLANS SUBMITTED OR | | | MECHANICAL CONTRACTOR INDICATED ON | | | PERMIT APPLICATION.PLEASE PROVIDE THE | | | FOLLOWING WITH MECHANICAL PERMIT | | | APPLICATION: | | | 1.INDICATE DUCT AND GRILLE SIZE, | | | MATERIAL AND LAYOUT. | | | | | | 2.PLAN SHEET A5 INDICATES AHU IN THE | | | ATTIC.PROVIDE DETAIL AS TO HOW THE | | | AHU IS MOUNTED. | | | | | | 3.AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED PER 2001 FBC(M) | | | 307.2.3. | | | | | | 4.PROVIDE LINE SET SIZES AS WELL AS | | | THE CONDENSATE. | | | | | | PLEASE NOTE ENERGY CALCS SUBMITTED WITH | | | BUILDING PERMIT.PLEASE PROVIDE MANUAL | | | J CALCULATIONS IN ACCORDANCE WITH 2001 | | | FBC CHAPTER 13 SUB-CHAPTER 6. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|