Plan Review Notes
Plan Review Notes For Permit 04061180
Permit Number 04061180
Review Stop M
Sequence Number 1
Notes
Date Text
2004-07-13 00:00:00NO MECHANICAL PLANS SUBMITTED OR
 MECHANICAL CONTRACTOR INDICATED ON
 PERMIT APPLICATION.PLEASE PROVIDE THE
 FOLLOWING WITH MECHANICAL PERMIT
 APPLICATION:
 1.INDICATE DUCT AND GRILLE SIZE,
 MATERIAL AND LAYOUT.
  
 2.PLAN SHEET A5 INDICATES AHU IN THE
 ATTIC.PROVIDE DETAIL AS TO HOW THE
 AHU IS MOUNTED.
  
 3.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.
  
 4.PROVIDE LINE SET SIZES AS WELL AS
 THE CONDENSATE.
  
 PLEASE NOTE ENERGY CALCS SUBMITTED WITH
 BUILDING PERMIT.PLEASE PROVIDE MANUAL
 J CALCULATIONS IN ACCORDANCE WITH 2001
 FBC CHAPTER 13 SUB-CHAPTER 6.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.