Plan Review Notes
Plan Review Notes For Permit 04061131
Permit Number 04061131
Review Stop B
Sequence Number 1
Notes
Date Text
2004-07-16 00:00:00DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
 PLANS MUST BE STAMPED BY PALM BEACH
 COUNTY.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED. NOC HAS EXPIRED.
 A NEW NOC WILL HAVE TO BE RECORDED.
  
 3) THE SECOND FLOOR PLAN ON A1 SHOWS
 BLOCKS ON EACH SIDE OF THREE OF THE
 WINDOWS. PLEASE CORRECT.
  
 4) SHOW INSULATION BETWEEN THE GARAGE
 AND THE CONDITIONED SPACE. FBC CHAPTER13
  
 5) SPECIFY THE LOCATION AND SIZE OF THE
 ACCESS TO ATTIC SPACE IN GARAGE AND SIZE
 OF ATTIC ACCESS ON SECOND FLOOR. SEE
 FBC 2309.6.
  
 6) A SECTION A ON A6 IS INDICATED ON THE
 FOUNDATION PLAN ON A2. THERE IS NO PLAN
 SHEET A6. PLEASE CORRECT.
  
 7) SUBMIT ELEVATION DRAWINGS OF THE
 STRUCTURE.
  
 8) SUBMIT A FLOOR FRAMING PLAN.
  
 9) SPECIFY THE LOCATIONS AND MATERIAL
 THAT WILL BE USED FOR THE DRAFTSTOPPING
 OF THE FLOOR/CEILING ASSEMBLY INTO AREAS
 OF NO MORE THAN 500 SQFT. AS REQUIRED BY
 FBC 2305.2.2.
  
 10) PROVIDE DETAILS OF THE STEEL COLUMN
 AT THE ENTRY. SHOW DETAIL OF COLUMN CAP
 AND BASE. SPECIFY WELDS, DIMENSIONS,
 FASTENERS, EMBEDMENT, ETC.
  
 11) SHEET A4 SPECIFIES TRUSS CONNECTORS
 EMBEDDED INTO CONCRETE, HOWEVER, THE
 WALL SECTION ON A5 SPECIFIES 2X6 WOOD
 FRAME. PLEASE CORRECT.
  
 12) PLEASE REVISE THE CONNECTORS
 SPECIFIED IN THE NOTES ON A4. HUGHES IS
 NO LONGER IN BUSINESS AND SIMPSON ETA-20
 IS NO LONGER LISTED IN THE SIMPSON
 CATALOG. NEITHER HAS STATE PRODUCT
 APPROVAL.
  
 13) THE UPLIFT VALUES FOR THE SIMPSON
 MTSM 16 AND THE WTSM 16 ARE INCORRECT.
 SEE 2004 SIMPSON CATALOG FOR VALUES THAT
 DO NOT INCLUDE A ONE-THIRD INCREASE IN
 THE STEEL CALCULATIONS.
  
 14)REVISE DETAIL 3 ON A5. FBC 1707.4.4.2
 REQUIRES THE DOOR JAMB TO BE FULLY
 SUPPORTED BY THE BUCK.
  
 15) SPECIFY HOW ATTIC SPACE IS TO BE
 VENTED AS REQUIRED BY FBC 2309.7.
  
 16) REVISE WALL SECTIONS TO INDICATE
 INTERIOR FINISHES, INSULATION, FURRING,
 FIRESTOPPING, ETC. OF WALLS AND CEILING.
  
 17) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 18) SUBMIT STATE/LOCAL PRODUCT APPROVAL
 FOR DOUBLE INSWING DOORS AT ENTRY.
  
 19) PRODUCT APPROVALS FOR OUTSWING PATIO
 DOORS WAS SUBMITTED. THERE ARE NO DOORS
 OF THIS TYPE SHOWN ON THE PLANS. PLEASE
 SUBMIT ONLY PRODUCT APPROVALS FOR ITEMS
 ON PLANS.
  
 IF YOU HAVE QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714