| Date |
Text |
| 2004-07-16 00:00:00 | DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | PLANS MUST BE STAMPED BY PALM BEACH |
| | COUNTY. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. NOC HAS EXPIRED. |
| | A NEW NOC WILL HAVE TO BE RECORDED. |
| | |
| | 3) THE SECOND FLOOR PLAN ON A1 SHOWS |
| | BLOCKS ON EACH SIDE OF THREE OF THE |
| | WINDOWS. PLEASE CORRECT. |
| | |
| | 4) SHOW INSULATION BETWEEN THE GARAGE |
| | AND THE CONDITIONED SPACE. FBC CHAPTER13 |
| | |
| | 5) SPECIFY THE LOCATION AND SIZE OF THE |
| | ACCESS TO ATTIC SPACE IN GARAGE AND SIZE |
| | OF ATTIC ACCESS ON SECOND FLOOR. SEE |
| | FBC 2309.6. |
| | |
| | 6) A SECTION A ON A6 IS INDICATED ON THE |
| | FOUNDATION PLAN ON A2. THERE IS NO PLAN |
| | SHEET A6. PLEASE CORRECT. |
| | |
| | 7) SUBMIT ELEVATION DRAWINGS OF THE |
| | STRUCTURE. |
| | |
| | 8) SUBMIT A FLOOR FRAMING PLAN. |
| | |
| | 9) SPECIFY THE LOCATIONS AND MATERIAL |
| | THAT WILL BE USED FOR THE DRAFTSTOPPING |
| | OF THE FLOOR/CEILING ASSEMBLY INTO AREAS |
| | OF NO MORE THAN 500 SQFT. AS REQUIRED BY |
| | FBC 2305.2.2. |
| | |
| | 10) PROVIDE DETAILS OF THE STEEL COLUMN |
| | AT THE ENTRY. SHOW DETAIL OF COLUMN CAP |
| | AND BASE. SPECIFY WELDS, DIMENSIONS, |
| | FASTENERS, EMBEDMENT, ETC. |
| | |
| | 11) SHEET A4 SPECIFIES TRUSS CONNECTORS |
| | EMBEDDED INTO CONCRETE, HOWEVER, THE |
| | WALL SECTION ON A5 SPECIFIES 2X6 WOOD |
| | FRAME. PLEASE CORRECT. |
| | |
| | 12) PLEASE REVISE THE CONNECTORS |
| | SPECIFIED IN THE NOTES ON A4. HUGHES IS |
| | NO LONGER IN BUSINESS AND SIMPSON ETA-20 |
| | IS NO LONGER LISTED IN THE SIMPSON |
| | CATALOG. NEITHER HAS STATE PRODUCT |
| | APPROVAL. |
| | |
| | 13) THE UPLIFT VALUES FOR THE SIMPSON |
| | MTSM 16 AND THE WTSM 16 ARE INCORRECT. |
| | SEE 2004 SIMPSON CATALOG FOR VALUES THAT |
| | DO NOT INCLUDE A ONE-THIRD INCREASE IN |
| | THE STEEL CALCULATIONS. |
| | |
| | 14)REVISE DETAIL 3 ON A5. FBC 1707.4.4.2 |
| | REQUIRES THE DOOR JAMB TO BE FULLY |
| | SUPPORTED BY THE BUCK. |
| | |
| | 15) SPECIFY HOW ATTIC SPACE IS TO BE |
| | VENTED AS REQUIRED BY FBC 2309.7. |
| | |
| | 16) REVISE WALL SECTIONS TO INDICATE |
| | INTERIOR FINISHES, INSULATION, FURRING, |
| | FIRESTOPPING, ETC. OF WALLS AND CEILING. |
| | |
| | 17) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 18) SUBMIT STATE/LOCAL PRODUCT APPROVAL |
| | FOR DOUBLE INSWING DOORS AT ENTRY. |
| | |
| | 19) PRODUCT APPROVALS FOR OUTSWING PATIO |
| | DOORS WAS SUBMITTED. THERE ARE NO DOORS |
| | OF THIS TYPE SHOWN ON THE PLANS. PLEASE |
| | SUBMIT ONLY PRODUCT APPROVALS FOR ITEMS |
| | ON PLANS. |
| | |
| | IF YOU HAVE QUESTIONS PLEASE CALL: |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |