| 2004-07-15 00:00:00 | ************** UNSAT ************** |
| | |
| | PLEASE SEE SOME NOTES FROM FIRST REVIEW |
| | HAVE NOT YET BEEN ADDRESSED. |
| | |
| | 1)NOTE: PLEASE SHOW CIRCUITING ON PLANS |
| | AND CORRELATE WITH THE SUBMITTED PANEL |
| | SCHEDULE. |
| | |
| | 2)NOTE: PLEASE LIST/SHOW/INDICATE SIGN |
| | CIRCUIT AS REQUIRED PER 600.5 |
| | |
| | 3 )NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| | PLEASE SHOW PER |
| | 220.3,220.10,220.11,220.13 ETC. |
| | PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| | AT 125% PER 215.3,230.42 |
| | PLEASE SUBMIT LOAD CALCS FOR EXISTING |
| | SERVICE. PLEASE SEE WHAT WAS SUBMITTED |
| | FOR REFERENCE TO PREVIOUS PERMITS DOES |
| | NOT INDICATE LOAD CALCS. |
| | |
| | 4)NOTE; PLEASE SEE RISER, STILL DOES NOT |
| | INDICATE ANY CONDUIT TO NEW SUB-PANELS, |
| | FEEDERS, EQUIPMENT GRNDS ETC. |
| | 215.5,310.16,250.24,250.110,250.122 ETC |
| | |
| | 5)NOTE: PLEASE SEE LETTER FROM FPL FOR |
| | AVAILABLE FAULT CURRENT IS NOW ATTACHED |
| | BUT THERE IS NO INDICATION FOR RATING |
| | OF MAINS. 110.9 |
| | |
| | 6)NOTE: PLEASE SEE SUB PANELS ARE NOTED |
| | ON PLANS AS BEING 125A AND 150A? |
| | PLEASE VERIFY AND CORRELATE. |
| | |
| | 7)NOTE: PLEASE SEE TITLE BLOCK IS REQ'D |
| | TO HAVE THE PRINTED LICENSE # OF |
| | ENGINEER. FAC 61G15-23.002. FS 471.025 |
| | |
| | PLEASE SEE ATTACHED COPY OF FS 553.80(2) |
| | (B) WITH RESPECT TO DESIGN PROFESSIONAL, |
| | THIS IS GIVEN AS A NOTICE FOR PLANS |
| | FAILED FOR THE SECOND REVIEW WHICH HAVE |
| | ONE OR MORE OF THE SAME CODE COMMETS. |
| | THIS IS A NOTICE ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |