| 2004-06-22 00:00:00 | ************ UNSAT **************** |
| | |
| | 1)NOTE: PLEASE SHOW ALL MIN CIRCUITING |
| | ON PLANS AND CORRELATE W/ PANEL SCHEDULE |
| | -S TO BE SUBMITTED. |
| | PLEASE ALSO SEE 700.12E FOR EM/EXT LTS. |
| | PLEASE PROVIDE ALL CIRCUITING TO |
| | SEPARATE TENANT SPACES. |
| | |
| | 2)NOTE: PLEASE SEE PLANS AND PERMIT |
| | APPLICATION INDICATE TWO NEW SUB PANELS |
| | BEING INSTALLED , YET NO INFORMATION IS |
| | PROVIDED ON A RISER DIAGRAM ETC? |
| | ADDTIONAL SERVICES ARE NOT PERMITTED, |
| | MUST COME FROM EXSITING SERVICE. |
| | MAY HAVE ADDTIONAL METERS. |
| | |
| | 3 )NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| | PLEASE SHOW PER |
| | 220.3,220.10,220.11,220.13 ETC. |
| | PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| | AT 125% PER 215.3,230.42 |
| | PLEASE PROVIDE LOAD CALCS FOR EXSITING |
| | SERVICE. |
| | |
| | 4)NOTE: PLEASE INDICATE REQUIRED CIRCUIT |
| | PER 600.5 |
| | |
| | 5)NOTE: PLEASE PROVIDE USEAGE AND OR |
| | NEW/ EXSITING SHOW WINDOW RECEPTS REQ'D |
| | PER 210.62. |
| | |
| | 6)NOTE: PLEASE VERIFY A/C SYSTEMS AND |
| | WHICH SYSTEM IS FEEDING WHICH AREA. |
| | PLANS ONLY SHOW ONE AHU? |
| | PLEASE SHOW ALL, AND DISC'S PER 440.11 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |