| 2004-08-10 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 1 | | | | | | FROM PREVIOUS REVIEW: | | | 1) POOL LAYOUT SHALL REFLECT THE DRAIN | | | DETAIL. DRAIN DETAIL SHOWS PIPING FOR | | | MAIN DRAINS AND SPA DRAIN CONNECTING AT | | | THE CENTER OF THE DRAINS, BUT POOL LAY- | | | OUT SHOWS THE PIPING OFFSET FROM CENTER | | | OF DRAINS. THESE SUCTION INLETS SHALL BE | | | PLUMBED SUCH THAT WATER IS DRAWN THROUGH | | | THEM SIMULTANEOUSLY. SECTION 424.2.6.6.4 | | | PLEASE CORRELATE DETAIL WITH POOL LAYOUT | | | SECTION 104.2.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|