| Plan Review Notes For Permit 04061027 |
| Permit Number |
04061027 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-08-31 00:00:00 | ********* NOTES REDLINED ************** | | | | | | 1)NOTE: PLEASE SEE AHU AND OVEN ARE | | | SHOWN WITH A LOAD OF 6KW AND 1-POLE 15A | | | BRKR AND AHU AT 5KW W/ 1-POLE 20A BRKR? | | | THIS WAS NOTED ON PREVIOUS REVIEW. | | | | | | 2)NOTE: PLEASE SEE 210.8A6 FOR REQUIRED | | | GFI PROTECTION SERVING KITCHEN COUNTER- | | | -SPACE. | | | | | | 3)NOTE: NOTED, ALL NEW BRANCH CIRCUITS | | | FEEDING EXISTING BEDRMS TO HAVE ARC- | | | -FAULT PROTECTION. 2002 NEC 210.12 |
|