| Plan Review Notes For Permit 04061027 |
| Permit Number |
04061027 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-07-28 00:00:00 | ********* UNSAT ********************** | | | | | | 1)NOTE: PLEASE SEE PANEL SCHEDULE. | | | PLEASE CORRELATE LOADS ALONG WITH OCP. | | | PLEASE SEE AHU, SHOWS 5KW W/50A OCP, | | | 9.5KW OVEN W/ 40A OCP ETC. | | | | | | 2)NOTE: PLEASE SEE MISSING TWO SMALL | | | APPLIANCE CIRCUITS REQUIRED. 210.11C1 | | | | | | 3)NOTE: PLEASE SEE RECEPTS ARE SHOWN ON | | | DIMMERS. THIS IS NOT PERMITTED. | | | | | | 4)NOTE: PLEASE SEE LOAD CALCULATION | | | SUBMITTED SHOWS LOAD AT 288A'S ON A 200A | | | PANEL. PLEASE SUBMIT LOAD CALCS PER NEC | | | 220.31 | | | | | | 5)NOTE: PLEASE SEE ANY NEW BRANCH CIR- | | | -CUITS TO BEDRMS WILL REQUIRE ARC FAULT | | | PROTECTION. 2002 NEC 210.12B. PLEASE | | | SEE SD'S ?? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|