2004-07-28 00:00:00********* UNSAT **********************
  
 1)NOTE: PLEASE SEE PANEL SCHEDULE.
 PLEASE CORRELATE LOADS ALONG WITH OCP.
 PLEASE SEE AHU, SHOWS 5KW W/50A OCP,
 9.5KW OVEN W/ 40A OCP ETC.
  
 2)NOTE: PLEASE SEE MISSING TWO SMALL
 APPLIANCE CIRCUITS REQUIRED. 210.11C1
  
 3)NOTE: PLEASE SEE RECEPTS ARE SHOWN ON
 DIMMERS. THIS IS NOT PERMITTED.
  
 4)NOTE: PLEASE SEE LOAD CALCULATION
 SUBMITTED SHOWS LOAD AT 288A'S ON A 200A
 PANEL. PLEASE SUBMIT LOAD CALCS PER NEC
 220.31
  
 5)NOTE: PLEASE SEE ANY NEW BRANCH CIR-
 -CUITS TO BEDRMS WILL REQUIRE ARC FAULT
 PROTECTION. 2002 NEC 210.12B. PLEASE
 SEE SD'S ??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  