Plan Review Notes
Plan Review Notes For Permit 04061027
Permit Number 04061027
Review Stop P
Sequence Number 1
Notes
Date Text
2004-07-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT A-1 INDICATES NEW TUB IN NEW LO-
 CATION IN MASTER BATH, NEW WATER CLOSET
 AND LAV IN NEW LOCATION IN POWDER ROOM,
 AND NEW SINK IN NEW LOCATION IN KITCHEN.
 SUBMIT SANITARY AND WATER RISER DIAGRAMS
 SHOWING ALL NEW WORK AND HOW IT CONNECTS
 TO EXISTING RISERS. SHOW ALL PIPE SIZES,
 AND WATER HAMMER ARRESTORS REQUIRED BY
 SECTION 604.9. SECTION 104.3.1.1.
 2) SHT A-1 INDICATES A FLOOR DRAIN USING
 THE EXISTING SHOWER DRAIN. SUBMIT A DE-
 TAIL SHOWING HOW THE DRAIN WILL BE IN-
 STALLED AND HOW THE DRAIN WILL BE SEALED
 TO PREVENT WATER FROM LEAKING TO FLOOR
 BELOW.
 3) THE PERSONAL SIGNATURE OF THE ARCHIT-
 ECT SHALL APPEAR ON ALL DOCUMENTS TO BE
 FILED FOR PUBLIC RECORD. INITIALS ARE
 NOT ACCEPTABLE. PLEASE PROVIDE PROOF OF
 LEGAL SIGNATURE WITH DRIVERS LICENSE,
 VOTER REGISTRATION, OR ARCHITECTS STATE
 LICENSE WITH SIGNATURE. ALSO SUBMIT A
 SIGNED/SEALED/NOTORIZED LETTER FOR OUR
 FILES WITH LEGAL SIGNATURE. FAC 61G1-16.
 003 & FS 481.2055.
 4) FIRM LICENSE NUMBER REQUIRED ON TITLE
 BLOCK. FAC 61G1-16.004(2) & FS 481.2055.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]