| 2004-06-23 00:00:00 | *************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE SEE TITLE BLOCK IS TO |
| | CONTAIN ALL INFORMATION AS SETFORTH IN |
| | FAC 61G1-16.004.FS 481.219 |
| | PLEASE SEE FS'S REQUIRED "LEGAL SIGNAT- |
| | -URE" FOR ARCH/ FS 481.221. PLEASE |
| | PROVIDE A SIGNED, DATED AND SEALED |
| | LETTER STATING THIS IS YOUR LEGAL |
| | SIGNATURE. THIS LETTER MUST ALSO BE |
| | NOTARIZED. |
| | **WE HAVE HAD SOME ISSUES WITH FORGERIES |
| | AND NOW MAINTAIN A FILE FOR SIGNATURES |
| | OF ARCH'S AND ENGINEERS. |
| | |
| | 2)NOTE: PLEASE SEE KITCHEN LAYOUT,ONE |
| | NOTE MENTIONS NEW OUTLET FOR DRYER WITH |
| | ARROW, YET THAT CIRCUIT # ON SCHEDULE |
| | INDICATES FRIG?? |
| | |
| | 3)NOTE: PLEASE 2-POLE CIRCUIT IN KITCHEN |
| | IS LABELED CIRCUIT 3,4. PLEASE VERIFY, |
| | COOKTOP/OVEN. THIS APPEARS TO BE ON |
| | THE SAME PHASE? (B) |
| | |
| | 4)NOTE: PLEASE LABEL NEW CIRCUITS ALSO |
| | AND CORRELATE WITH PANEL SCHEDULE. PLANS |
| | SHOW EXISTING BUT NOT NEW? |
| | |
| | 5)NOTE: PLEASE VERIFY NEW OR EXSITING |
| | SD'S REQUIRED UNDER NFPA-72.8-1.4.1.6.2 |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | INSERT NEW REVISED SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SEE COMMENTS FROM OTHER TRADES |
| | THAT MAY OR MAY NOT HAVE AN AFFECT ON |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |