| 2006-01-30 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04061022 |
| | ADD: 605 N OLIVE AV |
| | CONT: CATALFUMO CONSTRUCTION |
| | TEL: (561)694-8818 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVISION REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-1.1 OFFICE 110 SEE 11-4.13.6 |
| | 11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARENCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARENCES SHALL BE |
| | CLEAR & LEVEL. |
| | |
| | 2) SHEET A-1.2 ROOMS 214 & 215 |
| | SHEET -5.2 DETAIL# 1 |
| | 11-4.13.6 MANEUVERING CLEARENCES |
| | AT DOORS. MINIMUM MANEUVERING CLEARENCES |
| | AT DOORS THAT ARE NOT AUTOMATIC OR |
| | POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARENCES SHALL BE |
| | CLEAR & LEVEL. |
| | |
| | 3)A 2.2 MISSING EXIT LIGHT IN HALLWAY |
| | BEFORE STAIR ENCLOSURE# 1. |
| | |
| | 4) 1 SEET OF MEP IS MISSING THE ENGINEER |
| | RAISED SEAL & SIGNATURE. |
| | PLANS, SPECIFICATIONS,REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN |
| | PROFESSIONAL AND BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |