Plan Review Notes
Plan Review Notes For Permit 04061022
Permit Number 04061022
Review Stop P
Sequence Number 5
Notes
Date Text
2005-09-10 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SANT. RISER DIAGRAM SHEETS. DRAWINGS
 SHALL BE DRAWN WITH SUFFICIENT CLARITY
 AND DETAIL TO INDICATE THE NATURE AND
 CHARACTER OF THE WORK. REVISIONS ARE NOT
 CLEAR TO THE WORK BEING DONE. SECTION
 104.2.1.
 2. SANT. RISER DIAGRAM SHEETS SIGNED AND
 SEALED BY AN ARCHITECT (NOT ARCHITECT OF
 RECORD) WITHOUT A REQUIRED TITLE BLOCK.
 FAC 61G1-16.004 & FS 481.2055.
 3. SHT A-03 A CLEANOUT IS REQUIRED NEAR
 THE JUNCTION OF THE BUILDING DRAIN AND
 THE BUILDING SEWER. SECTION 708.3.5.
 4. SHT A-03 SHOWS WATER LINE REVISION.
 IF WATER LINES ARE CHANGED, A REVISION
 IS REQUIRED FOR THE WATER RISER DIAGRAM.
 SECTION 104.3.1.1.
 5. SHT A-03 THE PRINTED NAME OF THE
 ARCHITECT IS REQUIRED IN THE TITLE
 BLOCK. FAC 61G1-16.004(6) & FS 481.2055
 6. SHT A-03 INDICATES A 2" SS LINE DOWN
 FROM THE SECOND FLOOR. IF THIS IS A
 REVISION THAN IT SHALL BE REFLECTED ON
 THE SANITARY RISER DIAGRAM. SECTION
 104.3.1.1.
  