| Plan Review Notes For Permit 04061022 |
| Permit Number |
04061022 |
|
| Review Stop |
P |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2005-09-10 00:00:00 | REVISION DENIED | | | REFERENCE: FBC-2001 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. SANT. RISER DIAGRAM SHEETS. DRAWINGS | | | SHALL BE DRAWN WITH SUFFICIENT CLARITY | | | AND DETAIL TO INDICATE THE NATURE AND | | | CHARACTER OF THE WORK. REVISIONS ARE NOT | | | CLEAR TO THE WORK BEING DONE. SECTION | | | 104.2.1. | | | 2. SANT. RISER DIAGRAM SHEETS SIGNED AND | | | SEALED BY AN ARCHITECT (NOT ARCHITECT OF | | | RECORD) WITHOUT A REQUIRED TITLE BLOCK. | | | FAC 61G1-16.004 & FS 481.2055. | | | 3. SHT A-03 A CLEANOUT IS REQUIRED NEAR | | | THE JUNCTION OF THE BUILDING DRAIN AND | | | THE BUILDING SEWER. SECTION 708.3.5. | | | 4. SHT A-03 SHOWS WATER LINE REVISION. | | | IF WATER LINES ARE CHANGED, A REVISION | | | IS REQUIRED FOR THE WATER RISER DIAGRAM. | | | SECTION 104.3.1.1. | | | 5. SHT A-03 THE PRINTED NAME OF THE | | | ARCHITECT IS REQUIRED IN THE TITLE | | | BLOCK. FAC 61G1-16.004(6) & FS 481.2055 | | | 6. SHT A-03 INDICATES A 2" SS LINE DOWN | | | FROM THE SECOND FLOOR. IF THIS IS A | | | REVISION THAN IT SHALL BE REFLECTED ON | | | THE SANITARY RISER DIAGRAM. SECTION | | | 104.3.1.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|