Plan Review Notes
Plan Review Notes For Permit 04061022
Permit Number 04061022
Review Stop M
Sequence Number 5
Notes
Date Text
2006-04-10 00:00:00PROVISO:
 1.EXHAUST SHALL NOT BE DIRECTED ONTO
 WALKWAYS OR TERMINATE IN A MANNER THAT
 CREATE A NUISANCE PER 2001 FMC 401.5.2.
  
 2.PLAN SHEET M7.2 INDICATES AUXILIARY
 DRAIN PAN ONLY REQUIRED FOR UNITS
 LOCATED ABOVE THE CEILING.PER 2001 FMC
 307.2.3 & 307.2.4, AN AUXULAIRY DRAIN
 PAN IS REQUIRED.THE FLOAT SWITCH SHALL
 BE INSTALLED IN THE AUXILIARY DRAIN PAN.
 PLEASE REVISE PLAN TO REFLECT THE
 REQUIREMENT OF ONE OF THE THREE METHODS
 DESCRIBED IN THE AFOREMENTIONED CODE
 SECTIONS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.