| Plan Review Notes For Permit 04061022 |
| Permit Number |
04061022 |
|
| Review Stop |
M |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2006-04-10 00:00:00 | PROVISO: | | | 1.EXHAUST SHALL NOT BE DIRECTED ONTO | | | WALKWAYS OR TERMINATE IN A MANNER THAT | | | CREATE A NUISANCE PER 2001 FMC 401.5.2. | | | | | | 2.PLAN SHEET M7.2 INDICATES AUXILIARY | | | DRAIN PAN ONLY REQUIRED FOR UNITS | | | LOCATED ABOVE THE CEILING.PER 2001 FMC | | | 307.2.3 & 307.2.4, AN AUXULAIRY DRAIN | | | PAN IS REQUIRED.THE FLOAT SWITCH SHALL | | | BE INSTALLED IN THE AUXILIARY DRAIN PAN. | | | PLEASE REVISE PLAN TO REFLECT THE | | | REQUIREMENT OF ONE OF THE THREE METHODS | | | DESCRIBED IN THE AFOREMENTIONED CODE | | | SECTIONS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|