| 2006-01-09 00:00:00 | ***** UNSAT ***** | | | | | | 1)NOTE: PLEASE SEE ONLY ONE SET IS | | | SIGNED, DATED AND SEALED BY THE ENGINEER | | | OF RECORD. | | | PLEASE SEE FAC 61G15-23.002 WHICH | | | REQUIRES ALL SETS TO BE SIGNED, DATED | | | AND SEALED. | | | PLEASE ALSO SEE THE SAME FLORIDA | | | ADMINISTRATIVE CODE WHICH REQUIRES THE | | | PRINTED NAME AND LICENSE # FOR SAID | | | ENGINEER OF TITLE BLOCK. | | | | | | ** PLEASE KNOW THIS IS REQUIRED FOR ALL | | | TRADES AND FOR ALL REVIEWER(S) WHETHER | | | OR NOT COMMENT IS MADE BY OTHER | | | REVIEWER(S). | | | | | | 2)NOT: PLEASE VERIFY OCP FOR AHU'S, HEAT | | | ETC TO BE SIZEDA MIN OF 125% PER | | | 424.3B | | | PLEASE ADJUST. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|