| 2005-06-10 00:00:00 | | | | *** ISSUED PERMIT*** | | | -PLAN REVIEW HISTORY- | | | | | | PERMIT# 04061022 | | | ADDRESS: 605 N. OLIVE AV. | | | CONT: CATALFUMO | | | TELL # (561) 307-4836 | | | | | | THE ATTACHED COMMENTS ARE PART OF THE | | | PERMIT AND PLAN REVIEW PACKAGE AND ARE | | | NOT TO BE REMOVED FROM THE ISSUED SET OF | | | PLANS.104.2.1.2 ADMINISTRATIVE CODE. | | | | | | BUILDING PROVISO: | | | PLANS ARE MISSING THESE PRODUCT APPROVAL | | | OR FLORIDA COVER SHEET OR DO NOT MEET | | | THE WIND PRESSURES REQUIRED FOR THIS | | | STRUCTURE. WINDOWS & DOORSWILL REQUIRE | | | REVIEWED NOA'S BY THE BUCK INSPECTION | | | (119). | | | ROOFING APPROVALS BEFORE FIRST ROOF | | | ASSEMBLIES INSPRCTION (112 ROOF METAL / | | | TIN TAG) | | | | | | MISSING APPROVALS: | | | | | | A) DENS-GLASS GOLD SHEATHING- LOW | | | PRESSURE | | | | | | B) JOHNS MANVILLE PVC OVER CONCRETE | | | NO FL COVER SHEET/ NO SYSTEMS | | | HIGHLIGHTED, SEE LIMITATIONS 7 & 9 FOR | | | PRESSURES | | | | | | C) ROOF APPROVALS: ENGLERT SERIES 2000 | | | METAL PANEL OVER STEEL DECK LOW PRESURES | | | GOOD FOR -62.5 REQUIRED -81.5. SYSTEM | | | LIMITATION SEE # 1, FOR ENHANCED | | | FASTENING. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | |
|