| 2004-10-19 00:00:00 | ********** UNSAT 2ND REVIEW ************ |
| | |
| | PLEASE SEE SOME NOTES FROM FIRST REVIEW |
| | STILL NEED TO BE ADDRESSED. |
| | |
| | 1)NOTE: NOTE#1 FROM PREVIOUS REVIEW. |
| | REPLY LETTER MENTIONS ADDED TO TITLE |
| | BLOCK, HOWEVER THIS COULD NOT BE LOCATED |
| | PLEASE SEE FAC 61G15-23.002. |
| | THIS IS REQUIRED ON ALL SHEETS AND FOR |
| | ALL TRADES WHEATHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWERS. |
| | |
| | 2)NOTE: NOTE#2 FROM PREVIOUS REVIEW. |
| | LETTER MENTIONS REVISED/ADDED FIXTURE |
| | TYPE ON E8.1, YET THIS WAS NOT FOUND. |
| | |
| | 3)NOTE: NOTE#5 FROM PREVIOUS REVIEW, |
| | PLEASE SEE 230.82 FOR EQUIPMENT PERMITT- |
| | -ED AHEAD OF MAIN. THIS IS NOT PERMITTED |
| | IN NEC. |
| | PLEASE ALSO SEE 230.72 |
| | |
| | 4)NOTE: NOTE#7 FROM PREVIOUS REVIEW. |
| | PLEASE SEE 310.16,240.4 ETC. SOME MOTOR |
| | ONLY LOADS (CU'S) ARE PERMITTED TO |
| | PROTECT AT THE NEXT SIZE UP.HOWEVER, |
| | AHU/HEAT ETC IS NOT, 424.3B ALONG W/ |
| | ABOVE. |
| | |
| | PLEASE SEE COPY OF FS 553.80(2)(B) FOR |
| | NOTICE ONLY GIVEN AT THIS TIME. |
| | |
| | PLEASE SEE POSSIBLE NOTES FROM OTHER |
| | REVIEWERS WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |