| 2004-07-10 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) SHT IRR-1 SEAL IMPRESSION DOES NOT |
| | SHOW ANY INFORMATION. PLEASE RESEAL TO |
| | IMPRESS INFORMATION REQUIRED BY FAC 61G1 |
| | -16.001/002 & FS 481.2055. |
| | 2) SHT A-1.3 SUBMIT CALCULATIONS FOR THE |
| | FLAT ROOF PER SECTIONS 1106 & 1107 AND |
| | ALL SUBSECTIONS. SHOW AREA OF ROOF WITH |
| | 1/2 AREA OF ALL VERTICAL WALLS INCLUDING |
| | PARAPETS AND ROOF AREAS THAT DRAIN ONTO |
| | THE ROOF FROM ABOVE SHOWN IN CALCULAT- |
| | IONS, |
| | 3) SHT A-1.3 COPPER SCUPPER DETAIL, IN- |
| | DICATE THE SIZE OF THE PIPE CONNECTED TO |
| | THE SCUPPER. SHOW PIPE SIZE FOR THE |
| | DOWNSPOUT. SECTION 1104.2.1 |
| | 4) SUBMIT A DETAIL FOR SECONDARY ROOF |
| | DRAIN. SHOW ALL PIPE SIZES, TERMINATION |
| | POINT, HEIGHT ABOVE ROOF SURFACE ECT. |
| | 5) SHTS A-1.1, A-1.2, & A-5.2 SINKS IN |
| | THE BREAK ROOMS, (119 & 223), AND CON- |
| | FERENCE ROOMS, (202 & 219), SHALL COMPLY |
| | WITH SECTION 11-4.24 AND ALL SUBSECTIONS |
| | SHOW HEIGHT 4.24.2, KNEE CLEARANCE 4.24. |
| | 3, DEPTH 4.24.4, CLEAR FLOOR SPACE 4.24. |
| | 5, EXPOSED PIPES AND SURFACES 4.24.6. |
| | 6) SHT A-7.2 FINISHED WALLS IN TOILET |
| | ROOMS CALL FOR WALL PAPER. THE WALLS AND |
| | FLOORS OF ALL PUBLIC REST ROOMS SHALL BE |
| | LINED WITH NONABSORBENT MATERIAL TO A |
| | HEIGHT OF 4 FT. ABOVE THE FLOOR. SECTION |
| | 1204.S (BLDG) - PLEASE CLARIFY. |
| | 7) SHTS P1.1 & P2.1 (SANT. RISER) MINI- |
| | MUM 2" PIPE UNDERGROUND. SECTION 710.3 |
| | 8) SHT P1.1 KEYED NOTES: 18 THRU 24, |
| | CONDENSATE SHALL DISCHARGE SEPARATELY |
| | FROM THE BUILDING AND TIE INTO STORM, A |
| | CATCH BASIN, OR DRYWELL. A RELIEF VENT, |
| | (GOOSENECK) SHALL BE INSTALLED AS THE |
| | CONDENSATE EXITS THE BUILDING. SECTION |
| | 90-125(5) CITY CODE. |
| | 9) SHT P2.1 WATER RISER DIAGRAM & KEY |
| | NOTES #4, WATER HAMMER ARRESTORS REQUIR- |
| | ED BY SECTION 604.9 SHALL BE LOCATED |
| | NEAR THE FIXTURE IN AN "EFFECTIVE RANGE" |
| | NOT IN THE CEILING AS SHOWN. PDI-WH 201 |
| | & MANUF. INSTALLATION INSTRUCTIONS. |
| | 10) SHTS P2.1 & P7.1 AS SHOWN ON THE |
| | WATER RISER DIAGRAM, THE WATER HEATER |
| | DETAIL, AND NOTE #2, THE VALVE ON THE |
| | DRAIN LINE FOR THE EMERGENCY DRAIN PAN |
| | FOR THE WATER HEATER IS NOT APPROVED. |
| | DELETE VALVE AND REFERENCE TO VALVE. |
| | 11) SUBMIT A DETAIL FOR THE DRINKING |
| | FOUNTAINS SHOWING COMPLIANCE WITH SECT- |
| | ION 11-4.15 AND ALL SUBSECTIONS. SHOW |
| | SPOUT HEIGHT 4.1.2, AND CLEARANCES/CLEAR |
| | FLOOR SPACE 4.15.5. |
| | 12) ADDRESS ON THE TITLE BLOCK IS NOT |
| | CORRECT. SEE ATTACHED SHEET. |
| | ENGINEERS SHALL LEGIBLY INDICATE THEIR |
| | NAME, ADDRESS AND LICENSE NUMBER ON EACH |
| | SHEET. IF PRACTICING THROUGH A DULY |
| | AUTHORIZED ENGINEERING BUSINESS, ENGIN- |
| | EERS, ENGINEERS SHALL LEGIBLY INDICATE |
| | THEIR NAME AND LICENSE NUMBER, AS WELL |
| | AS, THE NAME, ADDRESS AND CERTIFICATE OF |
| | AUTHORIZATION NUMBER OF THE ENGINEERING |
| | BUSINESS ON EACH SHEET. A TITLE BLOCK |
| | WILL SATISFY THIS REQUIREMENT. FAC |
| | 61G15-23.002(2) - FS 471.025 |
| | *********WHEN RESUBMITTING PLANS******** |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |