Plan Review Notes
Plan Review Notes For Permit 04061022
Permit Number 04061022
Review Stop P
Sequence Number 1
Notes
Date Text
2004-07-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT IRR-1 SEAL IMPRESSION DOES NOT
 SHOW ANY INFORMATION. PLEASE RESEAL TO
 IMPRESS INFORMATION REQUIRED BY FAC 61G1
 -16.001/002 & FS 481.2055.
 2) SHT A-1.3 SUBMIT CALCULATIONS FOR THE
 FLAT ROOF PER SECTIONS 1106 & 1107 AND
 ALL SUBSECTIONS. SHOW AREA OF ROOF WITH
 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS AND ROOF AREAS THAT DRAIN ONTO
 THE ROOF FROM ABOVE SHOWN IN CALCULAT-
 IONS,
 3) SHT A-1.3 COPPER SCUPPER DETAIL, IN-
 DICATE THE SIZE OF THE PIPE CONNECTED TO
 THE SCUPPER. SHOW PIPE SIZE FOR THE
 DOWNSPOUT. SECTION 1104.2.1
 4) SUBMIT A DETAIL FOR SECONDARY ROOF
 DRAIN. SHOW ALL PIPE SIZES, TERMINATION
 POINT, HEIGHT ABOVE ROOF SURFACE ECT.
 5) SHTS A-1.1, A-1.2, & A-5.2 SINKS IN
 THE BREAK ROOMS, (119 & 223), AND CON-
 FERENCE ROOMS, (202 & 219), SHALL COMPLY
 WITH SECTION 11-4.24 AND ALL SUBSECTIONS
 SHOW HEIGHT 4.24.2, KNEE CLEARANCE 4.24.
 3, DEPTH 4.24.4, CLEAR FLOOR SPACE 4.24.
 5, EXPOSED PIPES AND SURFACES 4.24.6.
 6) SHT A-7.2 FINISHED WALLS IN TOILET
 ROOMS CALL FOR WALL PAPER. THE WALLS AND
 FLOORS OF ALL PUBLIC REST ROOMS SHALL BE
 LINED WITH NONABSORBENT MATERIAL TO A
 HEIGHT OF 4 FT. ABOVE THE FLOOR. SECTION
 1204.S (BLDG) - PLEASE CLARIFY.
 7) SHTS P1.1 & P2.1 (SANT. RISER) MINI-
 MUM 2" PIPE UNDERGROUND. SECTION 710.3
 8) SHT P1.1 KEYED NOTES: 18 THRU 24,
 CONDENSATE SHALL DISCHARGE SEPARATELY
 FROM THE BUILDING AND TIE INTO STORM, A
 CATCH BASIN, OR DRYWELL. A RELIEF VENT,
 (GOOSENECK) SHALL BE INSTALLED AS THE
 CONDENSATE EXITS THE BUILDING. SECTION
 90-125(5) CITY CODE.
 9) SHT P2.1 WATER RISER DIAGRAM & KEY
 NOTES #4, WATER HAMMER ARRESTORS REQUIR-
 ED BY SECTION 604.9 SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE"
 NOT IN THE CEILING AS SHOWN. PDI-WH 201
 & MANUF. INSTALLATION INSTRUCTIONS.
 10) SHTS P2.1 & P7.1 AS SHOWN ON THE
 WATER RISER DIAGRAM, THE WATER HEATER
 DETAIL, AND NOTE #2, THE VALVE ON THE
 DRAIN LINE FOR THE EMERGENCY DRAIN PAN
 FOR THE WATER HEATER IS NOT APPROVED.
 DELETE VALVE AND REFERENCE TO VALVE.
 11) SUBMIT A DETAIL FOR THE DRINKING
 FOUNTAINS SHOWING COMPLIANCE WITH SECT-
 ION 11-4.15 AND ALL SUBSECTIONS. SHOW
 SPOUT HEIGHT 4.1.2, AND CLEARANCES/CLEAR
 FLOOR SPACE 4.15.5.
 12) ADDRESS ON THE TITLE BLOCK IS NOT
 CORRECT. SEE ATTACHED SHEET.
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]