| Plan Review Notes For Permit 04061022 |
| Permit Number |
04061022 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-06-29 00:00:00 | DENIED: | | | 1.PLAN SHEET M1.1, FIRE DAMPERS | | | REQUIRED ON DUCTS PENETRATING OR | | | TERMINATING AT A RATED WALL PER 2001 | | | FBC(M) 607.1.2.DUCTS TERMINATING AT | | | THE ELEV MACHINE RM, STORAGE RM, & ATM | | | RM ARE REQUIRED TO HAVE FIRE DAMPERS. | | | | | | 2.PLAN SHEET M7.2 DETAIL 1 NOTE 4, | | | AUXILIARY DRAIN PAN SHALL HAVE OVERFLOW | | | PROTECTION BY MEANS OF A FLOAT SWITCH OR | | | AUXILIARY DRAIN LINE TERMINATING AT A | | | CONSPICUOUS POINT PER 2001 FBC(M) | | | 307.2.3.PLEASE INDICATE WHICH METHOD | | | WILL BE UTILIZED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|