Plan Review Notes
Plan Review Notes For Permit 04061022
Permit Number 04061022
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-06-23 00:00:001) ELECTRONIC SWITCHES, CHAIN AND LOCK
 REQUIRED ON FIRE LINE BACKFLOW DEVICE.
  
 2) ARE ANY HANDRAILS PLANNED FOR
 STAIR TREADS AT THE EAST/NORTH ENTRY
 PORTICO.
  
 3) TACTILE SIGNAGE REQUIRED AT EXIT
 DOOR LOCATIONS.
  
 4) BUILDING ADDRESS REQUIRED ON PROPER
 ELEVATION. A MINIMUM OF 6" HIGH NUMBERS
 ARE REQUIRED.
  
 5) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR HANDRAILS AND
 GUARDRAILS.
  
 6) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER SYSTEM INSTALLATION.
 CONNECTION TO CITY MAIN MUST BE APPROVED
 BY CITY UTILITIES PRIOR TO SUBMITTING
 PLANS.
  
 7) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM. THE FIRE ALARM
 SYSTEM SHALL BE MONITORED BY A LICENSED
 UL COMPANY APPROVED FOR CENTRAL STATION
 SERVICE.
  
 8) NO COMBUSTIBLES ALLOWED IN THE
 RETURN AIR PLENUM.
  
 9) ELEVATOR WARNING SIGNS REQUIRED AT
 ELEVATOR ENTRANCES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910