| Plan Review Notes For Permit 04060959 |
| Permit Number |
04060959 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-07-01 00:00:00 | DENIED; | | | 1.NOTE 6. SHOULD READ, SHOCK ARRESTORS | | | TO BE INSTALLED PER SEC. 604.9. | | | 2.RISER DIAGRAM AND FLOOR PLAN FLAT LINE | | | DRAWING NOT TO CODE. | | | A.2ND FL TUB BATH, TUB IS NOT VENTED | | | B.L/T NOT SHOWN ON RISER DIAGRAM. | | | C.1ST FLOOR MASTER BATH W/M MUST TIE | | | IN DOWN STREAM OF THE BATHROOM | | | GROUP. SEE SEC. 909.1. | | | D.SIZE ALL PIPE ON FLAT DRAWING OR | | | RISER DIAGRAM. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|