| Date |
Text |
| 2004-07-08 00:00:00 | DENIED |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) SUBMIT TWO COPIES OF A RECENT SURVEY. |
| | |
| | 4) FBC* 1804.2.2AREA OF QUESTIONABLE |
| | SOIL.SUBMIT A GEOTECHNICAL REPORT |
| | TO VERIFY THE SAFE BEARING CAPACITY OF |
| | THE SOIL. |
| | |
| | 5) PLANS DO NOT CLEARLY INDICATE THE |
| | PROTION OF THE STRUCTURE THAT IS EXIST- |
| | ING. PLEASE CLARIFY. |
| | |
| | 6) THE FIRM LICENSE NUMBER IS NOT GIVEN |
| | IN THE TITLE BLOCK. SEE FAC 61G1-16.004. |
| | |
| | 7) A SEPARATE PERMIT IS REQUIRED FOR THE |
| | SITE WALLS. |
| | |
| | 8) THE FULL BATH ON THE FIRST FLOOR IS |
| | REQUIRED TO HAVE DOORS WITH 29" CLEAR |
| | OPENING PER FBC 11-4.22.2. |
| | |
| | 9) FBC MECHANICAL CODE 304.6 REQUIRES |
| | HEAT PRODUCING APPLIANCES TO MAINTAIN |
| | CLEARANCES TO COMBUSTABLE CONSTRUCTION, |
| | INCLUDING SHUTTERS AND DRAPES. LOCATION |
| | OF WINDOW ABOVE COOKTOP IN KITCHEN. |
| | |
| | 10) AT LEAST ONE WINDOW IN SECOND FLOOR |
| | BEDROOMS MUST COMPLY WITH EGRESS. SEE |
| | FBC 1005.4. THE (F) WINDOWS IN THE |
| | SCHEDULE ON SHEET 2 SHOULD BE MARKED |
| | EGRESS. |
| | |
| | 11) SPECIFY FIREBLOCKING AT CONCEALED |
| | SPACES BETWEEN STAIR STRINGERS AT THE |
| | TOP AND BOTTOM OF RUNS AS REQUIRED BY |
| | FBC 2305.1.4. |
| | |
| | 12) SPECIFY THE REQUIRED CLEARANCES OF |
| | EXISTING CHIMNEY FROM ROOF AND NEW |
| | CONSTRUCTION. SEE FBC 2804.2.4. |
| | |
| | 13) SHOW COMPLIANCE WITH FBC 1503.4.4 |
| | WHICH REQUIRES DOWNSPOUTS TO DISCHARGE |
| | AT LEAST 12" FROM SIDEWALLS OF THE |
| | STRUCTURE AND GUTTERS WITH DOWNSPOUTS ON |
| | BUILDINGS WITH EAVES OF LESS THAN 6" |
| | PROJECTIONS. |
| | |
| | 14) THE POSITIVE AND NEGATIVE SIGNS ARE |
| | MISSING FROM THE INTERNAL PRESSURE |
| | COEFFICENT ON SHEET 5. |
| | |
| | 15)TWO DIFFERENT SOIL BEARING CAPACITIES |
| | ARE GIVEN ON SHEET 5. PLEASE CORRECT. |
| | |
| | 16) TWO DIFFERENT STRENGTHS OF CONCRETE |
| | ARE SPECIFIED ON SHEET5. THE FOOTING |
| | SCHEDULE HAS 2500 PSI AND THE FOUNDATION |
| | PLAN LISTS 3000 PSI CONCRETE. PLEASE |
| | CORRECT. |
| | |
| | 17) SPECIFY HOW THE SECTION OF THE |
| | SECOND FLOOR BLOCK WALL AND CONC. COLUMN |
| | ABOVE THE EXISTING MASTER BEDROOM WILL |
| | BE SUPPORTED FROM BELOW. |
| | |
| | 18) REVISE THE DIAGRAM OF THE HIP ROOF |
| | NAILING ZONES ON SHEET 7. THE OUTSIDE |
| | CORNERS OF HIP ROOFS ARE ALSO ZONE 3. |
| | SEE CITY OF WPB AMENDMENTS TO FBC TABLE |
| | 2306.1. |
| | |
| | 19)SPECIFY FIREBLOCKING ON WALL SECTIONS |
| | FBC 2305.1.4 REQUIRES CONCEALED SPACES |
| | OF STUD WALLS AND PARTITIONS INCLUDING |
| | FURRED SPACES TO BE FIREBLOCKED AT |
| | CEILING AND FLOOR LEVELS AND WHERE WALLS |
| | AND FLOORS OR TRUSSES MEET. |
| | |
| | 20) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. |
| | SUBMIT PRODUCT APPROVALS FOR EXTERIOR |
| | WINDOWS, DOORS, MULLIONS, OVERHEAD |
| | GARAGE DOORS, ETC. |
| | |
| | 21) SUBMIT A KEY PLAN, INSTALLATION |
| | SCHEDULE AND PRODUCT APPROVAL FOR STORM |
| | PANELS (UNLESS IMPACT GLAZING IS USED). |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL: |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |