Plan Review Notes
Plan Review Notes For Permit 04060944
Permit Number 04060944
Review Stop E
Sequence Number 3
Notes
Date Text
2007-09-15 09:22:23 
 ** DENIEDREVISIONS**
  
 ** PLEASE SEE NOTES BELOW. ELECTRICAL RISER HAS NOW
 BEEN COMPLETELY REVISED.
  
 1) NOTE: PLEASE SEE RISER NOW INDICATES THE POOL PANEL
 AND THE CABANA PANEL BEING TAPPED FROM EACH OF THE TWO
 200AMP MAIN DISCONNECTS HOWEVER THE PANEL SCHEDULE FOR
 THE METER MAIN INDICATES ONE OF THESE PANELS FROM THAT
 PANEL.
 PLEASE SEE ORIGINAL RISER HAD BOTH OF THESE PANELS FROM
 THE METER MAIN.
 PLEASE SEE THE RISER CONDUCTORS/FEEDERS TO POOL PANEL
 ARE NOT THE SAME AS SCHEDULE.
 PLEASE SUBMIT PLANS SHOWING ALL LOCATIONS FOR EQUIPMENT
 AND PANELS. (UNABLE TO VERIFY TAPPED CONDUCTORS IF
 THESE PANELS ARE ACTUALLY BEING TAPPED FROM THESE
 MAINS)
 PLEASE SEE 240.21 FOR TAPPED CONDUCTOR RULES AS EACH OF
 THESE PANELS WOULD REQUIRE MAINS AND OVER CURRENT
 PROTECTION.
 240.21, 240.4, 310.16, 408.4 ETC
 FBC 104.1.2 (2001)
  
 2) NOTE: PLEASE SEE PREVIOUS REDLINED PLANS FROM JULY
 04 WHICH WAS NEVER CORRECTED OR REVISED.
 PLEASE SEE THE REVIEW REDLINES AT THAT TIME IS
 ATTACHED.
 THE MDP PANEL SCHEDULE WAS MISSING THE CABANA PANEL
 LISTED. 408.4
 THE UPSTAIRS CABANA BATH WAS MISSING.210.52D, 210.11C3
 PLEASE SEE THE LOAD CALCULATIONS WERE NEVER CORRECTED
 AS THE 1ST 10KW IS STILL BEING SHOWN AS A/C HEAT WHICH
 IS NOT CORRECT. PLEASE SEE 220.31
 ** PLEASE SUBMIT COMPLETE ELECTRICAL PLANS INCLUDING
 CABANA.
  
 3) NOTE: PLEASE SEE THE GROUNDING ELECTRODE SYSTEM AT
 THE MAIN HOUSE IS NO LONGER COMPLETE PER 250.32,
 250.50.
  
 4) NOTE: PLEASE SEE THE PANEL SCHEDULES ARE REQUIRED TO
 BE UPDATED PER 408.4. THE ITEMS AS SHOWN ARE THE SAME
 FROM THE 04 PLANS WHICH IS NOT CORRECT.
 PLEASE ALSO SEE THAT ALL ROOMS AND AREAS ON PANEL
 SCHEDULE ARE TO BE SPECIFIC.
 PLEASE SEE THE FOLLOWING TEXT WHICH IS EXTRACTED FROM
 THE CODE COMMENTARY UNDER 408.4.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 104.1.2
  
 5) NOTE: PLEASE SEE PLANS AND PANEL SCHEDULE INDICATE
 SMOKE DEVICES AS *SD* AND SYMBOL LEGEND HAS THESE AS
 SMOKE DETECTORS.
 PLEASE KNOW THAT A MEETING WAS HELD AT THE SOUTHERN
 SECTION MEETING IN OCT 06 WHERE WE WERE DIRECTLY
 INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE DETECTORS
 ON PLANS FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN
 THESE DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS
 OF SMOKE ALARMS WHICH WOULD BE SHOWN AS SA/SMOKE
 ALARMS.
 THIS AHJ HAS PERMITTED THE GENERAL USE OF THE SD FOR
 SMOKE DETECTORS AND WAS ALWAYS ACCEPTED.
 BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE*.
 PLEASE SEE NFPA-72 8-1.4.1.6.2 1999 AS PERMITTED.
  
 6) NOTE: PLEASE BE SURE THE ADOPTED CODES AT THE TIME
 OF PERMIT APPLICATION IS STATED ON PLANS.
 2001 FBC, 2002 NFPA-70 (NEC), 1999 NFPA-72
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]