| 2007-09-15 09:22:23 | |
| | ** DENIEDREVISIONS** |
| | |
| | ** PLEASE SEE NOTES BELOW. ELECTRICAL RISER HAS NOW |
| | BEEN COMPLETELY REVISED. |
| | |
| | 1) NOTE: PLEASE SEE RISER NOW INDICATES THE POOL PANEL |
| | AND THE CABANA PANEL BEING TAPPED FROM EACH OF THE TWO |
| | 200AMP MAIN DISCONNECTS HOWEVER THE PANEL SCHEDULE FOR |
| | THE METER MAIN INDICATES ONE OF THESE PANELS FROM THAT |
| | PANEL. |
| | PLEASE SEE ORIGINAL RISER HAD BOTH OF THESE PANELS FROM |
| | THE METER MAIN. |
| | PLEASE SEE THE RISER CONDUCTORS/FEEDERS TO POOL PANEL |
| | ARE NOT THE SAME AS SCHEDULE. |
| | PLEASE SUBMIT PLANS SHOWING ALL LOCATIONS FOR EQUIPMENT |
| | AND PANELS. (UNABLE TO VERIFY TAPPED CONDUCTORS IF |
| | THESE PANELS ARE ACTUALLY BEING TAPPED FROM THESE |
| | MAINS) |
| | PLEASE SEE 240.21 FOR TAPPED CONDUCTOR RULES AS EACH OF |
| | THESE PANELS WOULD REQUIRE MAINS AND OVER CURRENT |
| | PROTECTION. |
| | 240.21, 240.4, 310.16, 408.4 ETC |
| | FBC 104.1.2 (2001) |
| | |
| | 2) NOTE: PLEASE SEE PREVIOUS REDLINED PLANS FROM JULY |
| | 04 WHICH WAS NEVER CORRECTED OR REVISED. |
| | PLEASE SEE THE REVIEW REDLINES AT THAT TIME IS |
| | ATTACHED. |
| | THE MDP PANEL SCHEDULE WAS MISSING THE CABANA PANEL |
| | LISTED. 408.4 |
| | THE UPSTAIRS CABANA BATH WAS MISSING.210.52D, 210.11C3 |
| | PLEASE SEE THE LOAD CALCULATIONS WERE NEVER CORRECTED |
| | AS THE 1ST 10KW IS STILL BEING SHOWN AS A/C HEAT WHICH |
| | IS NOT CORRECT. PLEASE SEE 220.31 |
| | ** PLEASE SUBMIT COMPLETE ELECTRICAL PLANS INCLUDING |
| | CABANA. |
| | |
| | 3) NOTE: PLEASE SEE THE GROUNDING ELECTRODE SYSTEM AT |
| | THE MAIN HOUSE IS NO LONGER COMPLETE PER 250.32, |
| | 250.50. |
| | |
| | 4) NOTE: PLEASE SEE THE PANEL SCHEDULES ARE REQUIRED TO |
| | BE UPDATED PER 408.4. THE ITEMS AS SHOWN ARE THE SAME |
| | FROM THE 04 PLANS WHICH IS NOT CORRECT. |
| | PLEASE ALSO SEE THAT ALL ROOMS AND AREAS ON PANEL |
| | SCHEDULE ARE TO BE SPECIFIC. |
| | PLEASE SEE THE FOLLOWING TEXT WHICH IS EXTRACTED FROM |
| | THE CODE COMMENTARY UNDER 408.4. |
| | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 104.1.2 |
| | |
| | 5) NOTE: PLEASE SEE PLANS AND PANEL SCHEDULE INDICATE |
| | SMOKE DEVICES AS *SD* AND SYMBOL LEGEND HAS THESE AS |
| | SMOKE DETECTORS. |
| | PLEASE KNOW THAT A MEETING WAS HELD AT THE SOUTHERN |
| | SECTION MEETING IN OCT 06 WHERE WE WERE DIRECTLY |
| | INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE DETECTORS |
| | ON PLANS FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN |
| | THESE DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS |
| | OF SMOKE ALARMS WHICH WOULD BE SHOWN AS SA/SMOKE |
| | ALARMS. |
| | THIS AHJ HAS PERMITTED THE GENERAL USE OF THE SD FOR |
| | SMOKE DETECTORS AND WAS ALWAYS ACCEPTED. |
| | BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE |
| | DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL |
| | NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY |
| | HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF |
| | SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS |
| | SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS |
| | SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS |
| | FOR OTHER NEW HOMES. |
| | ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC |
| | RESIDENTIAL CODE/ FBC AND IN NFPA-72. |
| | IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE*. |
| | PLEASE SEE NFPA-72 8-1.4.1.6.2 1999 AS PERMITTED. |
| | |
| | 6) NOTE: PLEASE BE SURE THE ADOPTED CODES AT THE TIME |
| | OF PERMIT APPLICATION IS STATED ON PLANS. |
| | 2001 FBC, 2002 NFPA-70 (NEC), 1999 NFPA-72 |
| | |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |