Plan Review Notes
Plan Review Notes For Permit 04060944
Permit Number 04060944
Review Stop E
Sequence Number 1
Notes
Date Text
2004-06-23 00:00:00*********** UNSAT *****************
  
 ** PLEASE SEE PLANS ARE NOT COMPLETE AT
 THIS TIME FOR A COMPLETE REVIEW OF 2002
 NEC CODE COMPLIANCE.**
 THE FOLLOWING IS ONLY NOTES FOR WHAT IS
 SHOWN AT THIS TIME.
  
 1)NOTE: PLEASE SEE RISER DIAGRAM NEEDS
 TO BE COMPLETED.
 PLEASE SHOW WHAT IS FEEDING DETACHED
 BLDG.? PLEASE SEE MISSING CONDUCTORS
 FROM METER TO MAINS AND FROM PANEL 'B'
 TO PANEL 'C'.
  
 2)NOTE: PLEASE SEE MISSING GROUNDING
 ELECTRODE SYSTEM PER 250.50
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 4)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 PLEASE ALSO SEE DETACHED BLDG.
  
 5) NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 6 ) NOTE: PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52E
 DETACHED BLDG.
  
 7)NOTE: PLEASE SEE MISSING RECEPT REQ'D
 FOR A/C EQUIPMENT. 210.63
  
 8)NOTE: PLEASE ALSO SEE PLANS MISSING
 SHOWING A/C UNITS AND DISC'S PER 440.11
 DETACHED BLDG MISSING SAME.
 210.70
  
 9)NOTE: PLEASE SEE MISSING CONTROL OF
 LTS AT DETACHED BLDG AND SECURITY LTS.
  
 10)NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 11)NOTE: PLEASE SEE 225.31 FOR MEANS
 OF DISCONNECT AT DETACHED BLDGS.
  
 12)NOTE: PLEASE GROUNDING SYSTEM AT
 DEATCHED BLDG. PER 250.32
  
 13)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 14)NOTE: PLEASE ALSO SEE SOME AREAS ARE
 SHOWING A J-BOX WHERE A LT FIXTURE OF
 SOME SORT IS REQUIRED FOR EGRESS LIGHT-
 -ING. 210.70, LS 101 5-8
  
 15)NOTE:PLEASE SEE OCP SHOWN FOR 12KW
 RANGE/COOKTOP. SHOWN AT 40A??
  
 16)NOTE: PLEASE SEE MISSING RECEPTS
 IN CABANA BATHS. 210.52D,210.11C3
  
 17)NOTE: PLEASE SUBMIT PANEL SCHEDULES
 SHOWING ALL MIN REQUIRED DEDICATED
 CIRCUITS, TEC PER NEC 2002
 PLEASE ALSO INDICATE AWG, AND OCP FOR
 BRANCH CIRCUITS.
  
 18)NOTE: PLEASE INCLUDE ALL LICENSE
 #'S ON TITLE BLOCK AS REQUIRED PER
 FS 481.219/ FAC 61G1-16.004
 THIS COMMENT IS FOR ARCH'S FIRM.
 THIS COMMENT IS FOR ALL TRADES AND SHEET
 -S WHEATHER PR NOT COMMENT IS MADE BY
 OTHER REVIEWERS.
  
 19)NOTE: PLEASE SEE LEGEND, SYMBOL SHOWN
 FOR J-BOX IS NOT DETAILED AS A "FAN BOX"
 , PLANS MENTION FAN/LT IN SOME LOCATIONS
 FOR THE SAME SYMBOL. PLEASE CORRELATE.
  
 PLEASE NOTE: DUE TO THE FACT OF PLANS
 NOT BEING COMPLETE AT THIS TIME, THERE
 MAY BE OTHER COMMENTS ON NEXT REVIEW.
 PLEASE ADDRESS THE ABOVE COMMENTS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT ONLY NEW SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW