| 2004-06-23 00:00:00 | *********** UNSAT ***************** |
| | |
| | ** PLEASE SEE PLANS ARE NOT COMPLETE AT |
| | THIS TIME FOR A COMPLETE REVIEW OF 2002 |
| | NEC CODE COMPLIANCE.** |
| | THE FOLLOWING IS ONLY NOTES FOR WHAT IS |
| | SHOWN AT THIS TIME. |
| | |
| | 1)NOTE: PLEASE SEE RISER DIAGRAM NEEDS |
| | TO BE COMPLETED. |
| | PLEASE SHOW WHAT IS FEEDING DETACHED |
| | BLDG.? PLEASE SEE MISSING CONDUCTORS |
| | FROM METER TO MAINS AND FROM PANEL 'B' |
| | TO PANEL 'C'. |
| | |
| | 2)NOTE: PLEASE SEE MISSING GROUNDING |
| | ELECTRODE SYSTEM PER 250.50 |
| | |
| | 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 4)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | PLEASE ALSO SEE DETACHED BLDG. |
| | |
| | 5) NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210.8A-6 |
| | |
| | 6 ) NOTE: PLEASE SEE MISSING RECEPTS FOR |
| | FRONT AND/OR REAR OF DWELLING. |
| | 210.52E |
| | DETACHED BLDG. |
| | |
| | 7)NOTE: PLEASE SEE MISSING RECEPT REQ'D |
| | FOR A/C EQUIPMENT. 210.63 |
| | |
| | 8)NOTE: PLEASE ALSO SEE PLANS MISSING |
| | SHOWING A/C UNITS AND DISC'S PER 440.11 |
| | DETACHED BLDG MISSING SAME. |
| | 210.70 |
| | |
| | 9)NOTE: PLEASE SEE MISSING CONTROL OF |
| | LTS AT DETACHED BLDG AND SECURITY LTS. |
| | |
| | 10)NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | |
| | 11)NOTE: PLEASE SEE 225.31 FOR MEANS |
| | OF DISCONNECT AT DETACHED BLDGS. |
| | |
| | 12)NOTE: PLEASE GROUNDING SYSTEM AT |
| | DEATCHED BLDG. PER 250.32 |
| | |
| | 13)NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | 14)NOTE: PLEASE ALSO SEE SOME AREAS ARE |
| | SHOWING A J-BOX WHERE A LT FIXTURE OF |
| | SOME SORT IS REQUIRED FOR EGRESS LIGHT- |
| | -ING. 210.70, LS 101 5-8 |
| | |
| | 15)NOTE:PLEASE SEE OCP SHOWN FOR 12KW |
| | RANGE/COOKTOP. SHOWN AT 40A?? |
| | |
| | 16)NOTE: PLEASE SEE MISSING RECEPTS |
| | IN CABANA BATHS. 210.52D,210.11C3 |
| | |
| | 17)NOTE: PLEASE SUBMIT PANEL SCHEDULES |
| | SHOWING ALL MIN REQUIRED DEDICATED |
| | CIRCUITS, TEC PER NEC 2002 |
| | PLEASE ALSO INDICATE AWG, AND OCP FOR |
| | BRANCH CIRCUITS. |
| | |
| | 18)NOTE: PLEASE INCLUDE ALL LICENSE |
| | #'S ON TITLE BLOCK AS REQUIRED PER |
| | FS 481.219/ FAC 61G1-16.004 |
| | THIS COMMENT IS FOR ARCH'S FIRM. |
| | THIS COMMENT IS FOR ALL TRADES AND SHEET |
| | -S WHEATHER PR NOT COMMENT IS MADE BY |
| | OTHER REVIEWERS. |
| | |
| | 19)NOTE: PLEASE SEE LEGEND, SYMBOL SHOWN |
| | FOR J-BOX IS NOT DETAILED AS A "FAN BOX" |
| | , PLANS MENTION FAN/LT IN SOME LOCATIONS |
| | FOR THE SAME SYMBOL. PLEASE CORRELATE. |
| | |
| | PLEASE NOTE: DUE TO THE FACT OF PLANS |
| | NOT BEING COMPLETE AT THIS TIME, THERE |
| | MAY BE OTHER COMMENTS ON NEXT REVIEW. |
| | PLEASE ADDRESS THE ABOVE COMMENTS. |
| | |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| | INSERT ONLY NEW SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |