Plan Review Notes
Plan Review Notes For Permit 04060897
Permit Number 04060897
Review Stop B
Sequence Number 3
Notes
Date Text
2005-01-05 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)A NOTICE OF COMMENCEMENT WILL BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)PROVIDE THE IMPACT FEE RECEIPT.
  
 3.)SHEET S3-2 SHOWS DESIGN PRESSURES
 HIGHER THAN PRODUCT LIMITATIONS.
 PLEASE
 ADDRESS.PLEASE NOTE THAT LOWER
 PRESSURES ARE INDICATED ON S1.2.IF
 SHEET S3-2 IS REMOVED, PLEASE SUBMIT A
 LETTER FROM THE ENGINEER THAT THIS IS
 ACCEPTABLE AND THAT THE LOWER DESIGN
 PRESSURES SHOWN ON S1.2 ARE TO BE USED.
  
 4.)WHILE THE OTHER PRODUCTS ARE
 COMPLIANT WITH THE WORST CASE PRESSURES
 SHOWN ON S1.2, THE GARAGE DOOR IS NOT.
 PLEASE ADDRESS.
  
 5.)STATE OR LOCAL PRODUCT APPROVALS
 REQUIRED IN ADDITION TO TEST REPORTS.
 I
 HAVE OBTAINED THE STATE PRODUCT
 APPROVAL
 NUMBER FOR YOU FOR MOST OF THE
 PRODUCTS.
 THE MULLIONS AND SINGLE HUNG WINDOW
 HAVE
 LOCAL PRODUCT APPROVAL, SEE ATTACHED.
 A
 COPY SHOULD BE PLACED ON THE TOP OF
 EACH
 NOA (S/H AND MULLION ONLY).
  
 6.)PLEASE NOTE THAT THE ROOF PRODUCT
 IS COMPLIANT FOR THIS BUILDING BUT
 WOULD
 NOT BE COMPLIANT FOR THE BUILDINGS WITH
 A MEAN ROOF HEIGHT OF >33'; SEE PAGE 2
 OF PRODUCT APPROVAL, ITEM 4.2.
  
 7.)SEE PREVIOUS LIST, #32, WINDOW
 BUCK
 TO GIVE FULL SUPPORT OF THE WINDOW,
 FBC1707.4.4.2 (A7).
  
 8.)THE FIREBLOCK DETAIL FOR THE 2 HR
 SEPARATION IS NOT FOR 2 HOURS; 80
 MINUTES WAS PROVIDED.THE SOFFIT AND
 FASCIA ARE TO BE FIRE RETARDANT WOOD 4'
 ON EACH SIDE.
  
  
  