| 2005-01-05 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)A NOTICE OF COMMENCEMENT WILL BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)PROVIDE THE IMPACT FEE RECEIPT. |
| | |
| | 3.)SHEET S3-2 SHOWS DESIGN PRESSURES |
| | HIGHER THAN PRODUCT LIMITATIONS. |
| | PLEASE |
| | ADDRESS.PLEASE NOTE THAT LOWER |
| | PRESSURES ARE INDICATED ON S1.2.IF |
| | SHEET S3-2 IS REMOVED, PLEASE SUBMIT A |
| | LETTER FROM THE ENGINEER THAT THIS IS |
| | ACCEPTABLE AND THAT THE LOWER DESIGN |
| | PRESSURES SHOWN ON S1.2 ARE TO BE USED. |
| | |
| | 4.)WHILE THE OTHER PRODUCTS ARE |
| | COMPLIANT WITH THE WORST CASE PRESSURES |
| | SHOWN ON S1.2, THE GARAGE DOOR IS NOT. |
| | PLEASE ADDRESS. |
| | |
| | 5.)STATE OR LOCAL PRODUCT APPROVALS |
| | REQUIRED IN ADDITION TO TEST REPORTS. |
| | I |
| | HAVE OBTAINED THE STATE PRODUCT |
| | APPROVAL |
| | NUMBER FOR YOU FOR MOST OF THE |
| | PRODUCTS. |
| | THE MULLIONS AND SINGLE HUNG WINDOW |
| | HAVE |
| | LOCAL PRODUCT APPROVAL, SEE ATTACHED. |
| | A |
| | COPY SHOULD BE PLACED ON THE TOP OF |
| | EACH |
| | NOA (S/H AND MULLION ONLY). |
| | |
| | 6.)PLEASE NOTE THAT THE ROOF PRODUCT |
| | IS COMPLIANT FOR THIS BUILDING BUT |
| | WOULD |
| | NOT BE COMPLIANT FOR THE BUILDINGS WITH |
| | A MEAN ROOF HEIGHT OF >33'; SEE PAGE 2 |
| | OF PRODUCT APPROVAL, ITEM 4.2. |
| | |
| | 7.)SEE PREVIOUS LIST, #32, WINDOW |
| | BUCK |
| | TO GIVE FULL SUPPORT OF THE WINDOW, |
| | FBC1707.4.4.2 (A7). |
| | |
| | 8.)THE FIREBLOCK DETAIL FOR THE 2 HR |
| | SEPARATION IS NOT FOR 2 HOURS; 80 |
| | MINUTES WAS PROVIDED.THE SOFFIT AND |
| | FASCIA ARE TO BE FIRE RETARDANT WOOD 4' |
| | ON EACH SIDE. |
| | |
| | |
| | |