| 2004-11-30 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)ENTRY VESTIBULE FOR EACH UNIT IS |
| | OUTSIDE THE LOT LINE OF THE BUILDING. |
| | |
| | 3.)SEPARATE PERMITS REQUIRED FOR |
| | TRADES. |
| | |
| | 4.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE |
| | STAMPED |
| | AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION. |
| | |
| | 5.)ADDITIONAL FEES DUE (VALUE |
| | ADJUSTMENT, RADON).SEE ATTACHED. |
| | |
| | 6.)SUBMIT MULLION PRODUCT APPROVALS. |
| | |
| | 7.)FLORIDA STATE OR LOCAL PRODUCT |
| | APPROVALS REQUIRED FAC9B72. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 8.)SIGN THE OWNER/AGENT LINE OF THE |
| | ENERGY CALC. |
| | |
| | 9.)ENERGY CALC 9A SHOULD STATE COMMON |
| | WALL, 4.2. |
| | |
| | 10.) BALCONY GUARDRAIL 3-A6 SHOWS THE |
| | POST EMBEDDED IN A CONCRETE SLAB, |
| | 10-S2.2 AND FLOOR FRAMING PLAN SHOWS |
| | THIS BALCONY AS HOLLOW CORE. |
| | |
| | 11.)2-A5 SHOWS THE EDGE OF THE HOLLOW |
| | CORE BEARING ON THE 2 HR PARTITION |
| | BLOCK |
| | WALL.SHOW HOW THE STRUCTURAL AND FIRE |
| | RESISTANCE IS MAINTAINED PER |
| | FBC704.4.2. |
| | THIS DETAIL CONFLICTS WITH THE |
| | STRUCTURALS (SHOWS CONCRETE TOPPING |
| | THROUGH THE WALL). |
| | |
| | 12.)SEE PREVIOUS LIST, #31, PROVIDE |
| | INFORMATION TO SHOW HOW THE HOLLOW CORE |
| | PLAN WILL HANDLE THE LINE LOAD OF THE |
| | CMU WALLS. |
| | |
| | 13.)SEE PREVIOUS LIST, #32 WINDOW |
| | BUCK |
| | TO GIVE FULL SUPPORT OF THE WINDOW, |
| | FBC1707.4.4.2 (A7). |
| | |
| | 14.)A RESIDENT INSPECTOR REQUIRED DUE |
| | TO THE SCOPE AND NATURE OF THIS |
| | PROJECT. |
| | PLEASE CONTACT HAROLD PISKURA. |
| | |
| | 15.)PROVIDE A DETAIL FOR THE 2 HR |
| | SEPARATION OF UNITS THROUGH THE SOFFIT |
| | AREA. |
| | |
| | 16.)PLEASE PROVIDE A SURVEY.A PLAT |
| | WAS PROVIDED BUT A SURVEY IS ALSO |
| | REQUIRED. |
| | |
| | 17.)FBC1007.3.1(1), SUM OF TWO RISERS |
| | AND A TREAD TO BE 24-25", ENTRY |
| | VESTIBULE, A2.MANY UNITS ARE NOT IN |
| | COMPLIANCE; PLEASE CHECK ALL UNITS. |
| | |
| | |
| | |