| Plan Review Notes For Permit 04060892 |
| Permit Number |
04060892 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-11-18 00:00:00 | DENIED: BUILDING 3 UNIT 17 | | | MONACO - END UNIT: | | | | | | COMMENT FROM REVIEW DATED 7-20-04 WAS | | | NOT ADDRESSED.RETURN AIR JUMPER FROM | | | THE MASTER BEDROOM IS NOT SIZED | | | PROPERLY.ALL SUPPLY AIR INTO THE | | | MASTER SUITE IS TO BE INCLUDED FOR A | | | TOTAL OF SUPPY AIR INTO THAT AREA.R/A | | | JUMPER SHALL BE A MINIMUM OF 1 1/2 | | | TIMES | | | THAT OF THE SUPPLY AIR INTO THE MASTER | | | SUITE. | | | | | | PLEASE NOTE FAN SCHEDULE INDICATES EF-3 | | | GARAGE FAN.THIS IS NOT INDICATED ON | | | THE PLAN.PLEASE CLARIFY. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS @ (561)805-6719. | | | |
|