| Plan Review Notes For Permit 04060892 |
| Permit Number |
04060892 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-07-20 00:00:00 | DENIED:"MONACO MODEL" END-UNIT | | | 1.RETURN AIR FROM THE MASTER BEDROOM | | | IS NOT SIZED PROPERLY.PER THE REVISED | | | 2001 FBC(M) 601.4 EXCEPTION #1; TRANSFER | | | DUCTS SHALL BE A MINIMUM OF 1 1/2 TIMES | | | THE SQUARE INCHES OF THE SUPPLY AIR TO | | | THAT SPACE.EXCEPTION #3; ALL AIR INTO | | | THE MASTER SUITE SHALL BE INCLUDED.SEE | | | THE ATTACHED SCHEDULE FOR PROPER SIZING | | | OF THE RETURN AIR JUMPER. | | | | | | 2.PROVIDE OUTSIDE AIR CALCULATIONS PER | | | 2001 FBC(M) 402.2, 402.2.1 OR 403.3. | | | | | | 3.AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED PER 2001 FBC(M) | | | 307.2.3. | | | | | | 4.PLANS ARE TO BE SIGNED AND DATED BY | | | THE PERSON RESPONSIBLE FOR THE DESIGN OF | | | THE HVAC SYSTEM IN ACCORDANCE WITH THE | | | FLORIDA STATUTES AND THE FLORIDA | | | ADMINISTRATIVE CODE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|