| 2004-06-24 00:00:00 | **************** UNSAT ************** |
| | BLDG #3 |
| | |
| | 1)NOTE: PLEASE SHOW CIRCUITING ON PLANS |
| | AND CORRELATE WITH SUBMITTED PANEL |
| | SCHEDULE. |
| | |
| | 2)NOTE: PLEASE SEE MISPRINT ON PLANS |
| | FOR ARC FAULT PROTECTION 210.12 |
| | |
| | 3)NOTE: PLEASE SEE OCP FOR AHU IS MUCH |
| | LARGER THAN OCP FO CU, YET LOAD CALCS |
| | INDICATE CU LOAD.? |
| | PLEASE CORRLEATE W/ MECH PLANS. |
| | |
| | 4)NOTE: PLEASE SEE NFPA-72 8-1.4.2, |
| | SD LOCATIONS. 3'FROM BATHS/KITCHENS, |
| | 5' FROM RA'GRILLES, 3'FROM SUPPLY, |
| | 20' FROM COOKING APPLIANCE, W/ EXCEPT. |
| | |
| | 5)NOTE: PLEASE SHOW A/C CU DISCONNECTS |
| | PER 440.11 |
| | |
| | 6)NOTE: PLEASE SEE FAC 61G15-23.002 AND |
| | FS 471.023. |
| | PLEASE INCLUDE ALL RQUIRED LICENSE #'S |
| | ON TITLE BLOCK. |
| | PLEASE SEE ATTACHED PRINT OUT FROM STATE |
| | DBPR'S SITE. FIRM SHOWN ON TITLE BLOCK |
| | HAS A "CLOSED" LICENSE? |
| | PLEASE SEE THE ABOVE IS REQUIRED FOR ALL |
| | TRADES AND SHEETS WHEATHER OR NOT |
| | COMMENTS ARE MADE BY OTHER REVIEWERS. |
| | |
| | PLEASE SEE COMMENTS FROM OTHER REVIEWERS |
| | AS THEY MAY HAVE AN AFFECT ON ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |