| Plan Review Notes For Permit 04060888 |
| Permit Number |
04060888 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-07-19 00:00:00 | DENIED:"MONACO MODEL" MID-UNIT | | | 1.EVERY PERMIT APPLCIAITON IS REQUIRED | | | TO HAVE A MINIMUM OF 2 COPIES OF PLANS | | | AND SPECIFICATIONS FOR REVIEW PER 2001 | | | FBC(M) 104.2.1. | | | | | | 2.PROVIDE OUTSIDE AIR CALCULATIONS PER | | | 2001 FBC(M) 402.2, 402.2.1 OR 403.3. | | | | | | 3.AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED PER 2001 FBC(M) | | | 307.2.3. | | | | | | 4.PLANS ARE TO BE SIGNED AND DATED BY | | | THE PERSON RESPONSIBLE FOR THE DESIGN OF | | | THE HVAC SYSTEM IN ACCORDANCE WITH THE F | | | LORIDA STATURTES AND THE FLORIDA | | | ADMINISTRATIVE CODE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|