| Date |
Text |
| 2004-07-19 00:00:00 | ****CORRECTIONS**** |
| | |
| | BLDG 1 - 04060859, 04060870, 04060872, |
| | 04060874, 04060875, 04060878 |
| | |
| | BLDG 2 - 04060879, 04060881, 04060883, |
| | 04060884, 04060886 |
| | |
| | BLDG 3 - 04060897, 04060896, 04060895, |
| | 04060894, 04060893, 04060892 |
| | |
| | BLDG 4 - 04060754, 04060721 |
| | |
| | BLDG 5 - 04060887, 04060888, 04060889, |
| | 04060890, 04060891 |
| | |
| | BLDG 6 - 04060861, 04060863, 04060865, |
| | 04060866 |
| | |
| | BLDG 7 - 04060867, 04060868 |
| | |
| | BLDG 8 - 04060856, 04060855 |
| | |
| | BLDG 9 - 04060842, 04060786 |
| | |
| | BLDG 10- 04060869, 04060871, 04060873 |
| | |
| | BLDG 11- 04060880, 04060882 |
| | |
| | BLDG 12 - 04060876, 04060877 |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.)SEPARATE PERMITS REQUIRED FOR |
| | TRADES. |
| | |
| | 3.)DECLARE A CONSTRUCTION TYPE. SHEET |
| | A1, CODE COMPLIANCE, REFERS TO BOTH |
| | TYPE IV UNPROTECTED AND TYPE IV 1 HR. |
| | THE PLANS MUST COMPLY WITH THE |
| | CONSTRUCTION TYPE DECLARED. |
| | |
| | 4.)PROVIDE AREA CALCS FOR THE UNITS |
| | INCLUDING CONDITIONED AND UNCONDITIONED |
| | SPACE. |
| | |
| | 5.)PROVIDE THE PRINTED NAME OF THE |
| | PERSON WHO PREPARED THE ENERGY CALCS. |
| | SIGN THE OWNER/AGENT LINE OF THE ENERGY |
| | CALCS. |
| | |
| | 6.)THE JURISDICTION NUMBER FOR THE |
| | ENERGY CALCS IS 604700.FOR EACH |
| | UNIT TYPE, INCLUDE THE PERMIT NUMBERS. |
| | |
| | 7.)FLORIDA STATE, LOCAL OR SITE |
| | SPECIFIC PRODUCT APPROVALS REQUIRED |
| | IN ADDITION TO THE TEST REPORTS.FAC9B72. |
| | WWW.FLORIDABUILDING.ORG |
| | PRODUCT APPROVALS NOT SUBMITTED PROPERLY |
| | BEFORE ISSUANCE WILL REQUIRE SEPARATE |
| | PERMITS FOR THOSE ITEMS. |
| | |
| | 8.)FOR UNITS WHICH HAVE A NEGATIVE |
| | DESIGN PRESSURE OF -126.4 (S3.2), THIS |
| | EXCEEDS THE PRODUCT LIMITATION (SEE |
| | PRODUCT APPROVAL, WINDOW). |
| | |
| | 9.) THE KD WINDOW PRODUCT APPROVALS ARE |
| | ILLEGIBLE.PROVIDE LEGIBLE COPIES |
| | SO THAT THEY CAN BE REVIEWED FOR CODE |
| | COMPLIANCE.PROVIDE WINDOW MULLION |
| | PRODUCT APPROVALS. |
| | |
| | 10.) INDICATE WHICH ANCHORS ARE BEING |
| | USED FOR THE HURRICANE SHUTTERS; |
| | COMPLETE AN INSTALLATION SCHEDULE (SEE |
| | ATTACHED). |
| | |
| | 11.) PROVIDE PRODUCT APPROVALS AND |
| | TEST REPORTS FOR THE SHINGLES AND FLAT |
| | TILE.MAY BE SUBMITTED WITH ROOF |
| | PERMIT APPLICATION.PLEASE NOTE ANY |
| | HEIGHT LIMITATION WHICH MAY BE ON THE |
| | SHINGLE PRODUCT APPROVAL. |
| | |
| | 12.) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY BEFORE A PERMIT CAN BE |
| | ISSUED.THE PLANS MUST BE STAMPED AND |
| | THE RECEIPT ATTACHED TO THE APPLICATION. |
| | 233-5025 |
| | |
| | 13.)PROVIDE A SOILS INVESTIGATION |
| | REPORT. |
| | |
| | 14.)PROVIDE A SURVEY FOR THIS |
| | PROPERTY. |
| | |
| | 15.)FOR ARCHITECTS, SEE FAC61G1-16. |
| | 003, 004.THE PRINTED NAME OF THE |
| | PERSON SEALING THE PLAN IS TO BE ON |
| | EACH SHEET.THE SEAL IS TO BE LEGIBLE. |
| | |
| | 16.)SHEET S1.2, ROOF FRAMING PLAN, |
| | SHOWS THE TRUSSES AS WOOD WHICH IS NOT |
| | CONSISTENT WITH OTHER NOTES AND DETAILS |
| | ON THE PLAN. |
| | |
| | 17.)SHOW HOW THE STRUCTURAL INTEGRITY |
| | AND FIRE RESISTANCE OF THE 2 HR TENANT |
| | SEPARATION WALL WILL BE MAINTAINED WITH |
| | THE PENETRATION OF THE FLOOR SYSTEM. |
| | SHOW HOW THE WALL WILL MAINTAIN ITS |
| | STRUCTURAL INTEGRITY INDEPENDENT OF THE |
| | UNIT ON THE OPPOSITE SIDE OF THE WALL. |
| | FBC704.4.2.; SECTION 2-A5.INCLUDE |
| | THE SHEATHING WHEN SHOWING THE |
| | INDEPENDENCE OF THE STRUCTURAL |
| | INTEGRITY. |
| | |
| | 18.)PROVIDE CALCULATIONS TO SHOW THAT |
| | SOFFIT VENTS COMPLY WITH FBC2309.7. |
| | |
| | 19.)PROVIDE ATTIC ACCESS LOCATION. |
| | |
| | 20.)TWO WALL SECTIONS HAVE BEEN |
| | PROVIDED (END UNIT EXTERIOR, SECTION |
| | BETWEEN UNITS 22 & 23).PLEASE PROVIDE |
| | A TYPICAL DETAIL FOR THE CONDITION |
| | WHICH OCCURS BETWEEN 20/21, 21/22, 23/24 |
| | DUE TO ELEVATION CHANGES.ALSO SHOW |
| | FOR OTHER BUILDINGS WHERE THIS |
| | CONDITION APPLIES. |
| | |
| | 21.)A 1X2 FIRESTOP IS SHOWN ON SECTION |
| | B-A4.THIS IS REQUIRED AT ALL FLOORS |
| | FBC705.3. |
| | |
| | 22.)SECTION 3-A5, THE TENANT |
| | SEPARATION OPTION, HOW WILL THIS WALL |
| | SUPPORT THE STEEL TRUSSES?PLEASE ALSO |
| | REWORD THE SECTION; CURRENTLY STATES |
| | "OPTIONAL" BUT THE SEPARATION IS |
| | MANDATORY.I BELIEVE THIS SHOULD BE |
| | "OPTION". |
| | |
| | 23.)SECTION 3-A5, PROVIDE MORE DETAIL |
| | SPECIFIC TO UL DESIGN U411.FOR |
| | INSTANCE, THE GYPSUM BOARD IS SHOWN |
| | DOUBLE GRAPHICALLY BUT SHOULD BE IN |
| | PRINT AS WELL, ALONG WITH THE ATTACHMENT |
| | REQUIRED BY UL411. |
| | |
| | 24.)ROOF/CEILING ASSEMBLIES ARE TO BE |
| | OF NONCOMBUSTIBLE CONSTRUCTION IN TYPE |
| | IV PER FBC TABLE 600.NOTE E STATES |
| | THAT FIRE RETARDANT TREATED WOOD IS TO |
| | BE USED IN BUILDINGS NOT OVER TWO |
| | STORIES.PLEASE ADDRESS. |
| | |
| | 25.)SECTION 1-A5 SHOWS FIRE RESISTANT |
| | PLYWOOD ON THE ENTIRE ROOF; 2-A5 APPEARS |
| | TO SHOW IT FOR 4' ONLY. |
| | |
| | 26.)SPECIFY INSULATION ON THE |
| | WALL SECTIONS. |
| | |
| | 27.)PROVIDE A BALCONY GUARDRAIL |
| | DETAIL; COMPLY WITH 1608.2.2 AND 1015. |
| | |
| | 28.)YOU CANNOT GIVE CODE REFERENCES |
| | AS A SPECIFICATION (SUCH AS SECTION2-A6) |
| | FBC104.2.1.PROVIDE DETAILS AND VERBAGE |
| | IN COMPLIANCE WITH THE CODE SECTIONS. |
| | SHOW ATTACHMENT FOR THE HANDRAIL |
| | TO COMPLY WITH 1608.2.1. |
| | |
| | 29.) 4-S2.3 SHOWS A GIRDER TRUSS WITH |
| | PLYWOOD; TYPE IV DOES NOT ALLOW |
| | COMBUSTIBLE/UNPROTECTED.OTHER DETAILS |
| | ALSO SHOW WOOD, WOOD CONNECTORS. |
| | IT APPEARS THAT THE STRUCTURALS SHOW |
| | WOOD, ARCHITECTURALS SHOW METAL TRUSSES. |
| | DETERMINE THE BUILDING TYPE AND |
| | MAKE ALL DETAILS CODE COMPLIANT. |
| | |
| | 30.)THE CONNECTOR HUS210-2 IS A |
| | WOOD TO WOOD USED IN A WOOD TO MASONRY |
| | OR CONCRETE APPLICATION (ROOF FRAMING |
| | HOLD DOWN ANCHOR SCHEDULE, S1.2). |
| | PROVIDE ALLOWABLE UPLIFT FOR HETA20. |
| | FASTENING OF PA28 CONFLICTS WITH |
| | CATALOG.ADDRESS. |
| | |
| | 31.)PROVIDE INFORMATION TO SHOW HOW |
| | THE HOLLOW CORE PLANK WILL HANDLE |
| | THE LINE LOAD OF THE CMU WALLS. |
| | |
| | 32.) WINDOW BUCK TO GIVE FULL SUPPORT |
| | OF THE WINDOW, FBC1707.4.4.2 (A7). |
| | |
| | 33.) S.01, PRE-ENGINEERED WOOD TRUSSES |
| | GIVE REFERENCE TO DESIGN CRITERIA FOR |
| | THE TRUSSES IN THE CONTRACT DOCUMENTS. |
| | PLEASE PROVIDE ON THE PLAN. |
| | |
| | 34.) S1.2, ROOF UPLIFT SCHEDULE, ZONE |
| | 3 IS TO COMPLY WITH CITY OF WEST PALM |
| | BEACH AMENDMENTS TO THE FBC, CHAPTER |
| | 23 REVISED 2306.1. |
| | |
| | 35.) WHEN RESUBMITTING, REPLACE ONLY |
| | SHEETS WHICH HAVE CHANGED.SUBMIT OLD |
| | SHEETS SEPARATELY.INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED. |
| | |
| | 36.) GENERAL COMMENT; ON SOME OF THE |
| | PLANS SOME SHEETS WERE UNSEALED |
| | PHOTOCOPIES.FAC61G15-23.002 REQUIRES |
| | THAT ALL SETS ARE ORIGNAL SIGNED, |
| | SEALED AND DATED PLANS.DO NOT SUBMIT |
| | PHOTOCOPIES OF SEALED DOCUMENTS. |
| | |
| | 37.) THE GARAGE JAMB DETAIL C-A6 |
| | CONFLICTS WITH THE ATTACHMENT ON THE |
| | PRODUCT APPROVAL SUBMITTED. |
| | |
| | 38.) PROVIDE FIRE SPRINKLER PLANS; |
| | FBC104.3.1.1, MINIMUM PLAN REVIEW |
| | CRITERIA, RESIDENTIAL, ITEM #3. |
| | |
| | 39.) ON THE SITE PLAN, CLEARLY INDICATE |
| | THE DISTANCE FROM EACH BUILDING TO THE |
| | PROPERTY LINE, AS WELL AS THE PROPERTY |
| | LINE TO THE CENTER OF THE ROAD FOR |
| | REVIEW FOR TABLE 600 COMPLIANCE.THIS |
| | APPEARS FOR SOME BUILDINGS (FOR EXAMPLE, |
| | BUILDING #2) BUT NOT OTHERS.ALSO NOTE |
| | THE DISTANCE BETWEEN 6 AND 7.IT IS |
| | UNCLEAR AS TO THE DISTANCE TO THE |
| | PROPERTY LINE AND TO CENTERLINE OF THE |
| | STREET ON THE REAR OF BUILDING 11. |
| | BUILDING 10 DIMENSIONS ARE NOT LEGIBLE. |
| | PROVIDE THE DISTANCE BETWEEN BUILDING |
| | 12 AND THE CABANA.IF NECESSARY TO |
| | SHOW TABLE 600 COMPLIANCE, PROVIDE |
| | AN ELEVATION OF THE CABANA (WEST SIDE). |
| | |
| | 40.) INDICATE RISE AND RUN FOR THE |
| | ENTRY STAIRS. |
| | |
| | 41.) ADDITIONAL FEES WILL BE DUE (VALUE |
| | ADJUSTMENT) AFTER CORRECT CONDITIONED |
| | AND UNCONDITIONED SQUARE FOOTAGE IS |
| | DETERMINED. |
| | |
| | 42.) PROVIDE A FIREBLOCKING DETAIL FOR |
| | THE DROPPED SOFFIT FBC705.3.1.1 AND |
| | THE STAIR FBC2305.1.5 (A6). |
| | |
| | 43.) SHEET S01, WOOD TRUSSES NOTE 2 |
| | REFERS TO TPI-85.THE CORRECT |
| | REFERENCE IS TPI 95, FBC2319.17.2. |
| | |
| | 44.) PROVIDE THE MEAN ROOF HEIGHT. |
| | BEFORE RESUBMITTAL CONFIRM THAT THE |
| | MEAN ROOF HEIGHT DOES NOT EXCEED THE |
| | PRODUCT LIMITATION, IF ANY, OF THE |
| | ROOF SHINGLE PRODUCT APPROVAL. |
| | |
| | 45.)DUE TO THE SCOPE AND NATURE OF |
| | THE CONSTRUCTION, A RESIDENT INSPECTOR |
| | WILL BE REQUIRED.PLEASE CONTACT |
| | HAROLD PISKURA, 561-805-6711. |
| | |
| | 46.)MASTER BATH WINDOWS ARE TO COMPLY |
| | WITH FBC2405.2.1(2) IF THEY ARE WITHIN |
| | 36".PLEASE NOTE ON FLOOR PLAN. |
| | |
| | THE FOLLOWING COMMENTS APPLY TO |
| | BUILDINGS 7, 8, 11 IN ADDITION TO THE |
| | PREVIOUS COMMENTS. |
| | |
| | 47.) THE SIDE ELEVATION DOES NOT |
| | COMPLY WITH TABLE 600 (TYPE |
| | IV, 10-20' IS LIMITED TO 20% OF |
| | OPENINGS). |
| | |
| | 48.) PROVIDE PRODUCT INFORMATION FOR |
| | THE 4 HOUR BLOCK REFERENCED UL901, SHEET |
| | A6.SEE NOTE 1, THE CONCRETE BLOCK IS |
| | TO BEAR THE UL CLASS MARKING.PLEASE |
| | NOTE THAT THIS BLOCK IS NOT READILY |
| | AVAILABLE LOCALLY. |
| | |
| | 49.) IT APPEARS THAT YOU ARE BUILDING |
| | ON AN EXISTING WALL.THIS WALL IS |
| | INDICATED ON B-A4 AS UL901.PROVIDE |
| | A PERMIT NUMBER AND PLANS SHOWING |
| | THE EXISTING WALL CONSTRUCTION. RE |
| | DETAIL 3-S2.4, SPECIFY EMBEDMENT INTO |
| | EXISTING WALL. |
| | |
| | 50.)THE FOOTING CANNOT ENCROACH |
| | THE PROPERTY LINE.ADDRESS. |
| | |
| | 51.)SHEET S3.9, BUILDING 11, REAR |
| | ELEVATION IS INCORRECTLY NOTED AS |
| | FRONT ELEVATION. |
| | |
| | 52.)FOR BUILDING 10, PRODUCT APPROVALS |
| | FOR OUTSWING DOOR W/SIDELITES WAS |
| | SUBMITTED; CANNOT LOCATE THIS PRODUCT |
| | ON THE PLAN. |
| | |
| | THE FOLLOWING COMMENT APPLIES TO BLDG |
| | 6 ONLY |
| | |
| | 53.)SECTION 2-A5 SHOWS THE 3RD FLOOR |
| | HOLLOW CORE PLANKS AS NOT BEARING ON |
| | THE WALL.CLARIFY. |
| | |
| | THE FOLLOWING COMMENTS APPLIES TO UNIT |
| | 36, BUILDING 10 ONLY |
| | |
| | 54.)THE FIRST FLOOR DEN IS CONSIDERED |
| | A BEDROOM BY FBC CHAPTER 13 DEFINITIONS. |
| | PLEASE RELABEL THIS ROOM. |
| | |
| | 55.)SHOW A FIREBLOCKING DETAIL BETWEEN |
| | ETIENNE AND MARSEILLE (OVERHANG |
| | ENCROACHES THE PROPERTY LINE). |
| | |
| | 56.)PROVIDE A COPY OF THE PEDESTRIAN/ |
| | UTILITY EASEMENT.PLEASE NOTE THAT |
| | PLAN REVIEW WILL INCLUDE CONFIRMING THAT |
| | THE PLANS CONFORM TO ALL OF THE |
| | REQUIREMENTS OF THE EASEMENT AND ZONING |
| | APPROVAL, INCLUDING ACCESS AND LIGHTING. |
| | |
| | 57.)THE LEFT SIDE OF THE PLAN IS NOT |
| | READABLE BECAUSE OF THE WAY IT IS |
| | STAPLED.PLEASE ENSURE THAT ALL PLANS |
| | ARE ENTIRELY READABLE. (SEE SHEET U2) |