| Plan Review Notes For Permit 04060879 |
| Permit Number |
04060879 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-06-24 00:00:00 | *************** UNSAT ************** | | | BLDG #2 | | | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH THE SUBMITTED | | | PANEL SCHEDULE. | | | | | | 2)NOTE: PLEASE SEE NFPA-72 8-1.4.2 FOR | | | SD LOCATIONS. PLEASE ALSO SEE EXCEPTIONS | | | | | | 3)NOTE: PLEASE SHOW A/C CU DISC LOCATION | | | -S 440.11 | | | | | | 4)NOTE: PLEASE SEE MISPRINT FOR 210.12 | | | ON E-8. | | | | | | 5)NOTE: PLEASE INCLUDE ALL REQUIRED | | | LICENSE #'S ON TITLE BLOCK FS 471.023 | | | AND FAC 61G15-23.002\ | | | PLEASE SEE ATTACHED COPY OF DBPR PRINT- | | | -OUT. THE FIRM SHOWN ON TITLE BLOCK IS | | | SHOWN AS HAVING A "CLOSED" LICENSE #. | | | THIS LICENSE # IS NOT ON TITLE BLOCK. | | | | | | 6)NOTE: PLEASE SEE OCP FOR AHU IS SHOWN | | | MUCH LARGER THAN CU, YET CU IS SHOWN | | | IN LOAD CALCS.? PLEASE ALSO CORRELATE | | | WITH MECH PLANS. | | | | | | PLEASE SEE COMMENTS FROM OTHER REVIEWERS | | | AS THEY MAY HAVE AN AFFECT ON ELECTRICAL | | | PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|