| Plan Review Notes For Permit 04060878 |
| Permit Number |
04060878 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-11-24 00:00:00 | DENIED:BUILDING 1 UNIT 6 | | | MONACO END UNIT | | | 1.THE RETURN AIR JUMPER FROM THE | | | MASTER SUITE IS NOT SIZED IN ACCORDANCE | | | WITH THE 2001 FBC(M) 601.4 EXCEPTION #1 | | | & 3.ALL SUPPLY AIR INTO THE MASTER | | | SUITE IS TO BE INCLUDED FOR THE TOTAL | | | AIR.RETURN AIR SHALL BE A MINIMUM OF | | | 16".PLEASE REVISE PLAN SHEET M-2. | | | | | | 2.PLEASE NOTE, ON PLAN SHEET M-2 THE | | | EXHAUST FAN SCHEDULE INDICATES EF-2 & | | | EF-3 WHICH ARE NOT IDENTIFIED ON THE | | | PLAN. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | |
|