| 2004-06-24 00:00:00 | *************** UNSAT *************** |
| | BLDG # 10 |
| | |
| | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED |
| | PANEL SCHEDULE. |
| | |
| | 2)NOTE: PLEASE SEE MISPRINT FOR NEC |
| | 210.12, 2002 NEC. |
| | |
| | 3)NOTE: PLEASE SEE NFPA-72 8-1.4.2 FOR |
| | SD LOCATIONS. 3'FROM BATHS/KITCHENS, |
| | SUPPLY GRILLES.5' FROM RA GRILLES, 20' |
| | FROM COOKING APPLIANCES. W/ EXCEPTIONS. |
| | |
| | 4)NOTE:PLEASE SEE OCP SHOWN FOR AHU IS |
| | SHOWN MUCH LARGER THAN CU OCP, YET |
| | LOAD CALCS SHOW CU LOAD AS GREATER LOAD? |
| | PLEASE CORRELATE WITH MECH PLANS AND |
| | ANY QUESTIONS ON SIZE OF HEAT KW FOR |
| | THIS SIZE UNIT. |
| | |
| | 5)NOTE: PLEASE SHOW DICONNECT AND LOCAT- |
| | -IONS ON ELECTRICAL PLANS. 440.11 |
| | |
| | 6)NOTE: PLEASE SEE FIRM SHOWN ON TITLE |
| | BLOCK, FRIM'S LICENSE # IS COMING UP |
| | AS CLOSED ON THE STATE DBPR WEBSITE. |
| | PLEASE INCLUDE ALL REQUIRED LICENSE #'S |
| | ON TITLE BLOCK PER 61G15-23.002 |
| | FS 471.023 |
| | PLEASE SEE # IS NOT SHOWN AT THIS TIME. |
| | THIS IS REQUIRED FOR ALL SHEETS AND ALL |
| | TRADES WHEATHER OR NOT COMMENT IS MADE |
| | BY OTHER REVIEWERS. |
| | |
| | PLEASE SEE NOTES FROM OTHER REVIEWS AS |
| | THEY MAY HAVE AN AFFECT ON ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |