| 2004-07-19 00:00:00 | DENIED:"BORDEAUX MODEL" UNIT 29 & 30 |
| | 1.PROVIDE OUTSIDE AIR CALCULATIONS PER |
| | 2001 FBC(M) 402.2, 402.2.1 OR 403.3. |
| | |
| | 2.AUXILIARY DRAIN PAN WITH OVERFLOW |
| | PROTECTION REQUIRED PER 2001 FBC(M) |
| | 307.2.3. |
| | |
| | 3.RETURN AIR JUMPER FROM THE MASTER |
| | BEDROOM IS NOT SIZED PROPERLY.PER THE |
| | REVISED 2001 FBC(M) 601.4 EXCEPTION #1; |
| | TRANSFER DUCTS SHALL BE A MINIMUM OF 1 |
| | 1/2 TIMES THE SQUARE INCHES OF THE |
| | SUPPLY AIR TO THAT SPACE.EXCEPTION #3; |
| | ALL AIR INTO THE MASTER SUITE IS TO BE |
| | INCLUDED.SEE THE ATTACHED SCHEDULE FOR |
| | PROPER SIZING. |
| | |
| | 4.PLANS ARE TO BE SIGNED AND DATED BY |
| | THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| | THE HVAC SYSTEM IN ACCORDANCE WITH THE |
| | FLORIDA STATUTES AND THE FLORIDA |
| | ADMINISTRATIVE CODE. |
| | |
| | 5.PLEASE CLARIFY RATING OF THE |
| | SEPARATION WALL BETWEEN THE GARAGE AND |
| | THE RESIDENCE. |
| | |
| | 6.PER 2001 FBC 104.2.1, TWO COPIES OF |
| | PLANS AND SPECIFICATIONS ARE TO BE |
| | PROVIDED FOR EACH PERMIT APPLICATION. |
| | PLEASE PROVIDE ADDITIONAL PLANS FOR |
| | COMPLIANCE. |
| | |