| 2004-06-24 00:00:00 | *************** UNSAT *************** |
| | BLDG # 7 |
| | |
| | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH SUBMITTED |
| | PANLE SCHEDULE. |
| | |
| | 2)NOTE: PLEASE SEE NFPA-72 FOR SD |
| | INSTALLATION LOCATIONS. |
| | 3'BATHS,LITS, 20' COOKING ETC. PLEASE |
| | ALSO SEE EXCEPTIONS. |
| | |
| | 3)NOTE: PLEASE SEE MISPRINT FOR ARC |
| | FAULT PROETCTION. NEC 210.12 E-8 |
| | |
| | 4)NOTE: PLEASE SEE CLOSET LT/ FIXTURE |
| | TYPE AND DISTANCE FROM SHELVES PER 410.8 |
| | |
| | 5)NOTE: PLEASE INDICATE A/C CU DISC'S |
| | PER 440.11 |
| | |
| | 6)NOTE: PLEASE SEE FAC 61G15-23.002, |
| | FS 471.023 |
| | PLEASE INCLUDE ALL LICENSE #'S ON TITLE |
| | BLOCK. |
| | PLEASE SEE ATTACHED COPY OF DBPR PRINT |
| | OUT OF WEB-SITE. FIRM AS SHOWN ON TITLE |
| | BLOCK IS SHOWN AS HAVING A "CLOSED" |
| | LICENSE #. |
| | PLEASE SEE ABOVE IS REQUIRED ON ALL |
| | SHEETS AND TITLE BLOCKS WHEATHER OR NOT |
| | COMMENT IS MADE BY OTHER REVIEWERS. |
| | |
| | 7)NOTE: PLEASE SEE OCP FOR AHU IS SHOWN |
| | LARGER THAN CU , YET LOAD CALCS SHOW |
| | CU LOAD? PLEASE CORRELATE WITH A/C PLANS |
| | |
| | PLEASE SEE COMMENTS FROM OTHER REVIEWERS |
| | AS THEY MAY HAVE AN AFFECT ON ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |