| Plan Review Notes For Permit 04060863 |
| Permit Number |
04060863 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-07-19 00:00:00 | DENIED:"GENEVA MODEL" MID-UNIT | | | 1.PLEASE NOTE, ONLY ONE PLAN PER SET | | | SUBMITTED FOR REVIEW.PLAN INDICATES | | | TWO GENEVA MID-UNITS.THEREFORE TWO | | | PLANS WILL BE REQUIRED PER SET.2001 | | | FBC(M) 104.2.1. | | | | | | 2.PROVIDE OUTSIDE AIR CALCULATIONS PER | | | 2001 FBC(M) 402.2, 402.2.1 OR 403.3. | | | | | | 3.AUXILIARY DRAIN PAN WITH OVERFLOW | | | PROTECTION REQUIRED PER 2001 FBC(M) | | | 307.2.3. | | | | | | 4.PLANS ARE TO BE SIGNED AND DATED BY | | | THE PERSON RESPONSIBLE FOR THE DESIGN OF | | | THE HVAC SYSTEM IN ACCORDANCE WITH THE | | | FLORIDA STATUTES AND THE FLORIDA | | | ADMINISTRATION CODE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|