| 2004-06-24 00:00:00 | *************** UNSAT ************ |
| | BLDG. #1 |
| | |
| | 1)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH THE SUBMITTED |
| | PANEL SCHEDULE. |
| | |
| | 2)NOTE: PLEASE SEE NFPA-72 FOR SD |
| | LOCATIONS. 3'FROM BATHS/KITCHENS, 5' |
| | FROM RA GRILLES, 3' SUPPLY, 20' |
| | FROM COOKING APPLIANCES W/ EXCEPTIONS. |
| | 8-1.4.2 |
| | |
| | 3)NOTE: PLEASE SHOW DISC'S FOR A/C CU'S. |
| | 440.11 |
| | |
| | 4)NOTE: PLEASE SEE MISPRINT FOR 210.12 |
| | ARC FAULT IS UNDER 2002 NEC. |
| | |
| | 5)NOTE: PLEASE SEE OCP FOR AHU IS SHOWN |
| | MUCH LARGER THAN OCP FOR CU, YET LOAD |
| | ON LOAD CALCS REFER TO CU LOAD? |
| | PLEASE CORRELATE WITH MECH PLANS FOR |
| | A HOUSE THIS SIZE. |
| | |
| | 6)NOTE: PLEASE SEE FAC 61G15-23.002 AND |
| | FS 471.023. PLEASE INCLUDE ALL REQUIRED |
| | LICENSE #'S ON TITLE BLOCK. |
| | PLEASE SEE FIRM SHOWN ON TITLE BLOCK |
| | NOW IS SHOWN AS HAVING A "CLOSED" |
| | LICENSE WITH STATE DBPR. |
| | SEE ATTACHED PRINT OUT. |
| | |
| | PLEASE SEE COMMENTS FROM OTHER REVIEWERS |
| | WHICH MAY AFFECT ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |