| 2004-11-01 00:00:00 | DENIED:BUILDING 8 UNIT 31 | | | "BORDEAUX/END UNT" | | | COMMENTS #2 & 3 FROM REVEIW DATED | | | 7-20-04 WERE NOT ADDRESSED: | | | | | | 2.RETURN AIR JUMPER FROM THE MASTER | | | BEDROOM IS NOT SIZED PROPERLY.A | | | MINIMUM OF 16" IS REQUIRED FOR | | | COMPLIANCE WITH 2001 FBC(M) 601.4 | | | EXCEPTION #1 & 3. | | | | | | 3.PLEASE CLARIFY RATING BETWEEN THE | | | GARAGE AND THE DEN.PLAN M-5 INDICATES | | | DUCT PENETRATING THIS WALL.PROVIDE | | | DETAIL OF THE SEPARATION WALL/CEILING | | | ASSEMBLY FOR THIS PENETRATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS @ (561)805-6719 |
|