| 2004-10-06 00:00:00 | ********** UNSAT 3RD REVIEW ********* |
| | |
| | **PLEASE SEE SOME NOTES FROM FIRST TWO |
| | REVIEWS STILL NEED TO BE ADDRESSED. |
| | |
| | 1)NOTE: PLEASE SEE FAC 61G15-23.002 AND |
| | FS 471.023 FOR REQUIRED MISSING INFORMAT |
| | -ION ON TITLE BLOCKS. |
| | PLEASE ALSO SEE FBC 104.2.1 FOR PERSON |
| | RESPONSIBLE FOR PLANS. |
| | NOTE#2 FROM PREVIOUS REVIEW. |
| | |
| | 2)NOTE: PLEASE SEE NOTE #3 FROM PREVIOUS |
| | REVIEW. PLEASE SUBMIT LOAD CALCULATIONS |
| | PER 2002 NEC 220.31B. 215.5 |
| | |
| | 3)NOTE: PLEASE SEE A NEW RISER DIAGRAM |
| | IS NOW BEING SUBMITTED FOR REVIEW. |
| | PLEASE CORRELATE RISER, PANEL SCHEDULE |
| | SPECS AND LEGEND TO THE LEFT OF RISER. |
| | ONE SHOWS PANEL "A" AS A 100A PANEL, |
| | OTHER 125A, ALSO 60A? |
| | |
| | 4)NOTE: PLEASE SEE NOTE BELOW RISER |
| | MENTIONS THIS GARAGE IS ATTACHED, YET |
| | PLANS SHOW THIS BLDG AS DEATCHED ON |
| | BLDG AND ELECTRICAL PLANS?? |
| | PLEASE SEE 250.32 FOR GROUNDING AT |
| | DETACHED BLDGS. |
| | |
| | 5)NOTE: PLEASE SEE ROOM/PORCH WITH MISS- |
| | -ING EGRESS LTS. 210.70 |
| | RECEPTS? 210.52 |
| | |
| | 6)NOTE: PLEASE SEE 210.52D,210.11C3 FOR |
| | REQUIRED CIRCUIT FOR BATH NOT SHOWN ON |
| | PANEL SCHEDULE. |
| | |
| | 7)NOTE: PLEASE SEE ARC-FAULT PROTECTION |
| | WILL BE REQUIRED FOR CABANA/ADAPTABLE |
| | SLEEPING RM. FOR RECEPTS/LTS/SD. |
| | 2002 NEC 210.12 |
| | |
| | 8)NOTE: PLEASE SEE ATTACHED COPY OF |
| | FS 553.80(2)(B) WITH RESPECT TO DESIGN |
| | PROFESSIONAL. THIS IS ONLY A NOTICE |
| | GIVEN AT THIS TIME. HOWEVER ONE COPY OF |
| | EACH SET IS NOW BEING RETAINED FOR FILE |
| | AND POSSIBLE REVIEW BY THE FBPE'S. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |