Plan Review Notes
Plan Review Notes For Permit 04060853
Permit Number 04060853
Review Stop E
Sequence Number 3
Notes
Date Text
2004-10-06 00:00:00********** UNSAT 3RD REVIEW *********
  
 **PLEASE SEE SOME NOTES FROM FIRST TWO
 REVIEWS STILL NEED TO BE ADDRESSED.
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002 AND
 FS 471.023 FOR REQUIRED MISSING INFORMAT
 -ION ON TITLE BLOCKS.
 PLEASE ALSO SEE FBC 104.2.1 FOR PERSON
 RESPONSIBLE FOR PLANS.
 NOTE#2 FROM PREVIOUS REVIEW.
  
 2)NOTE: PLEASE SEE NOTE #3 FROM PREVIOUS
 REVIEW. PLEASE SUBMIT LOAD CALCULATIONS
 PER 2002 NEC 220.31B. 215.5
  
 3)NOTE: PLEASE SEE A NEW RISER DIAGRAM
 IS NOW BEING SUBMITTED FOR REVIEW.
 PLEASE CORRELATE RISER, PANEL SCHEDULE
 SPECS AND LEGEND TO THE LEFT OF RISER.
 ONE SHOWS PANEL "A" AS A 100A PANEL,
 OTHER 125A, ALSO 60A?
  
 4)NOTE: PLEASE SEE NOTE BELOW RISER
 MENTIONS THIS GARAGE IS ATTACHED, YET
 PLANS SHOW THIS BLDG AS DEATCHED ON
 BLDG AND ELECTRICAL PLANS??
 PLEASE SEE 250.32 FOR GROUNDING AT
 DETACHED BLDGS.
  
 5)NOTE: PLEASE SEE ROOM/PORCH WITH MISS-
 -ING EGRESS LTS. 210.70
 RECEPTS? 210.52
  
 6)NOTE: PLEASE SEE 210.52D,210.11C3 FOR
 REQUIRED CIRCUIT FOR BATH NOT SHOWN ON
 PANEL SCHEDULE.
  
 7)NOTE: PLEASE SEE ARC-FAULT PROTECTION
 WILL BE REQUIRED FOR CABANA/ADAPTABLE
 SLEEPING RM. FOR RECEPTS/LTS/SD.
 2002 NEC 210.12
  
 8)NOTE: PLEASE SEE ATTACHED COPY OF
 FS 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONAL. THIS IS ONLY A NOTICE
 GIVEN AT THIS TIME. HOWEVER ONE COPY OF
 EACH SET IS NOW BEING RETAINED FOR FILE
 AND POSSIBLE REVIEW BY THE FBPE'S.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW