Plan Review Notes
Plan Review Notes For Permit 04060853
Permit Number 04060853
Review Stop P
Sequence Number 2
Notes
Date Text
2004-08-21 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SANT. RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN, NOR DOES IT MEET CODE
 REQUIREMENTS.
 A) SHOW ALL PIPE SIZES
 B) WASH MACHINE SHALL BE LOCATED DOWN-
 STREAM OF THE KITCHEN ON THE RISER DIAG-
 RAM AS IT IS SHOWN ON THE FLOOR PLAN.
 C) THE CABANA IS LOCATED TO THE NORTH-
 WEST CORNER OF THE LOT AND THE RISER
 DIAGRAM SHOWS THE CABANA CONNECTING
 PRIOR TO BATH #2 AND GOING TO THE SOUTH.
 D) WASH MACHINE REQUIRES A 2' STANDPIPE
 AND A CLEANOUT 4' ABOVE THE FLOOR FOR
 ACCESS. SECTIONS 1002.1/808.4 & 708.10
 PLEASE SUBMIT A RISER THAT REFLECT THE
 FLOOR PLAN AND MEETS CODE REQUIREMENTS.
 2)ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS AND LICENSE NUMBER ON EACH
 SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGIN-
 EERS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET. A TITLE BLOCK
 WILL SATISFY THIS REQUIREMENT. FAC
 61G15-23.002(2) - FS 471.025
  