| 2004-08-21 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1) SANT. RISER DIAGRAM DOES NOT REFLECT |
| | THE FLOOR PLAN, NOR DOES IT MEET CODE |
| | REQUIREMENTS. |
| | A) SHOW ALL PIPE SIZES |
| | B) WASH MACHINE SHALL BE LOCATED DOWN- |
| | STREAM OF THE KITCHEN ON THE RISER DIAG- |
| | RAM AS IT IS SHOWN ON THE FLOOR PLAN. |
| | C) THE CABANA IS LOCATED TO THE NORTH- |
| | WEST CORNER OF THE LOT AND THE RISER |
| | DIAGRAM SHOWS THE CABANA CONNECTING |
| | PRIOR TO BATH #2 AND GOING TO THE SOUTH. |
| | D) WASH MACHINE REQUIRES A 2' STANDPIPE |
| | AND A CLEANOUT 4' ABOVE THE FLOOR FOR |
| | ACCESS. SECTIONS 1002.1/808.4 & 708.10 |
| | PLEASE SUBMIT A RISER THAT REFLECT THE |
| | FLOOR PLAN AND MEETS CODE REQUIREMENTS. |
| | 2)ENGINEERS SHALL LEGIBLY INDICATE THEIR |
| | NAME, ADDRESS AND LICENSE NUMBER ON EACH |
| | SHEET. IF PRACTICING THROUGH A DULY |
| | AUTHORIZED ENGINEERING BUSINESS, ENGIN- |
| | EERS, ENGINEERS SHALL LEGIBLY INDICATE |
| | THEIR NAME AND LICENSE NUMBER, AS WELL |
| | AS, THE NAME, ADDRESS AND CERTIFICATE OF |
| | AUTHORIZATION NUMBER OF THE ENGINEERING |
| | BUSINESS ON EACH SHEET. A TITLE BLOCK |
| | WILL SATISFY THIS REQUIREMENT. FAC |
| | 61G15-23.002(2) - FS 471.025 |
| | |